Editorial Technical Reference

Output filter (LC filter)

Inverter output LC (sine wave) filters · Three-phase low-pass filters between a PWM motor drive and the motor, rated 3.3–1,320 A, with inductance from 11.7 to 0.12 mH, Y-connected capacitors from 4.7 to 816 µF, minimum switching frequencies of 1.5–6 kHz and residual ripple under 5%

An output LC filter sits between a PWM inverter or motor drive and the motor. Its inductors and capacitors form a low-pass filter that turns the drive's rectangular pulse voltage into a near-sinusoidal voltage, protecting motor insulation and bearings and allowing long motor cables. Ask three things first: what drive voltage, current and switching frequency the filter must match, how long the motor cable is, and what voltage drop, ripple and losses the system can accept.

Three-phase LC sine wave output filters for PWM inverters and variable frequency drives feeding motors or step-up transformers. Mains-side power-line EMI filters (see emi filter), discrete filter inductors (see filter inductor), dv/dt filters, input line reactors, and grid-tie LCL filters are outside this page.

CNFX editorial research · Sources checked October 12, 2026 · 4 sources

Output Filter (LC Filter) in a manufacturing environment
Representative product image. Confirm appearance and specifications with the manufacturer.

01

Match drive voltage, current and switching frequency

Schaffner describes the FN 5040 HV as an LC sine wave filter that converts the rectangular PWM output voltage of motor drives into a smooth sine wave with low residual ripple, addressing motor damage from high dv/dt, overvoltages, cable ringing, overheating and eddy current losses, reducing bearing currents, electromagnetic emissions and acoustic noise, and eliminating pulse reflections in the motor cable. [1]

Its selection table runs from the FN 5040HV-13 (13 A, 7.5 kW at 690 V/50 Hz, 11.7 mH, 4.7 µF, 170 W loss, 14 kg) to the FN 5040HV-1320 (1,320 A, 1,200 kW, 0.12 mH, 816 µF, 4,700 W, 945 kg). The minimum drive switching frequency is 2 kHz up to the 300 A model and 1.5 kHz above it; capacitors are Y-connected. Schaffner requires the drive to run in scalar (V/Hz) mode at a fixed switching frequency at or above the minimum, and cautions that wrong drive settings may damage the filter. [1]

VEIKONG's sine wave filters are rated 3 × 380 V ±10%, 5–120 Hz operating frequency, 2–16 kHz switching frequency, 1.5 to 630 kW and 3.3 to 1,209 A; its table lists minimum switching frequencies of 6 kHz for the smallest models, falling to 4 kHz at 24–32 A. [2]

Editorial calculation: a simple per-phase estimate f = 1/(2π√(LC)) gives about 679 Hz for 11.7 mH with 4.7 µF, 644 Hz for 1.3 mH with 47 µF, and 509 Hz for 0.12 mH with 816 µF, each below the 1.5–2 kHz minimum switching frequency; the datasheet does not state a resonant frequency, so ask the maker. [1]

MTE Corporation's selection table for its High Frequency SineWave Guardian, an open-panel filter for 380 V and 480 V drives feeding high-frequency motors, shows the link between switching frequency and the motor frequency a filter can pass. Its 24 listed models fall into three groups: 2 kHz models from 200 A to 1,200 A for a 6–200 Hz system frequency, 3.5 kHz models from 200 A to 650 A for 6–240 Hz, and 5 kHz models from 80 A to 600 A for 6–300 Hz. MTE says to select by the motor's full-load amps and, if the FLA exceeds the filter rating, to use the next larger filter; capacitors are included, and the product page lists a three-year warranty. MTE states that its SineWave Guardian range protects motors on leads out to 15,000 ft. [4]

Editorial calculation: in MTE's table the highest system frequency is one-tenth of the switching frequency at 2 kHz (200 Hz) and about one-seventeenth at 5 kHz (300 / 5,000), so a drive that must run a motor above 200 Hz needs a filter designed for the higher switching frequency; 15,000 ft is about 4,570 m, against the 2,000 m cable limit Schaffner gives for the FN 5040 HV. [4] [1]

Give the supplier the drive make and model, system voltage, rated and overload current, switching frequency and control mode, motor frequency range, motor cable length and type, number of motors in parallel, any step-up transformer, ambient temperature, enclosure and mounting, and the ripple, voltage drop and loss limits.

02

Check ripple, voltage drop, overload and cable length

Schaffner's FN 5040 HV is specified for 3 × 690 VAC ±10%, 0–70 Hz motor frequency (up to 200 Hz with derating), rated currents of 13–1,320 A at 45 °C, motor cables up to 2,000 m, impedance of 8–10% at 690 V, 50 Hz and rated current, residual ripple voltage under 5%, overload of 1.5 × rated current for 1 minute once per hour, IP00 protection, acoustic noise under 70 dB(A) at 1 m, insulation class EIS 200 and design to IEC 61558-2-20. With reduced motor cable length the maximum switching frequency is 16 kHz. [1]

VEIKONG lists residual ripple THD under 5%, a standard voltage drop of 4% at rated current and 50 Hz, maximum permanent overload of 1.2 × and transient overload of 2.0 × rated current, IP00 as standard, natural ventilation, floor mounting, ambient −25 to +40 °C, and recommends its filters for motor cables up to 500 m. It notes that IGBT switching can produce voltage peaks reaching 1,300 V or more at the motor terminals. [2]

Editorial calculation: 4% of 380 V is about 15.2 V. [2]

The US Department of Energy's motor systems tip sheets set out why such filters are fitted. Tip Sheet #14 (November 2012) cites NEMA MG 1-2011 Part 31: insulation for definite-purpose low-voltage (≤ 600 V) inverter-duty motors should withstand 3.1 times rated line-to-line voltage — 1,426 V peak at the terminals of a 460 V motor — with rise times of at least 0.1 µs, and such motors can run without filters or load reactors provided overshoots stay within that limit. It reports spikes as high as 2,150 V in a 480 V system at 10% overvoltage, and says that "damaging reflected waves are generally not a problem when the distance between the motor and the drive is less than 15 feet". Tip Sheet #15 adds that with modern IGBT switches "cable lengths of 50 feet or more almost always need mitigation", and lists line inductors or load reactors at the drive end of the cable, or dV/dt filters, where the drive cannot sit close to the motor. [3]

Editorial calculation: 3.1 × 460 V = 1,426 V, and the 2,150 V spike DOE reports is about 1.5 times that limit (2,150 ÷ 1,426); a sine wave filter removes the steep PWM edges that cause such overshoots, which is why Schaffner rates the FN 5040 HV for motor cables up to 2,000 m. [3] [1]

03

Find output LC filter manufacturers

The companies in the manufacturer list below show this product on their own websites. Confirm the legal seller, factory and scope for your order.

Ask any supplier for rated voltage and current, inductance and capacitance, minimum and maximum switching frequency, motor frequency range and derating, residual ripple, voltage drop or impedance, losses, overload, maximum cable length, insulation class and test voltages, protection rating and cooling, weight and dimensions, and drive settings required.

04

Trace what each part does

This is a functional reference built from the sources cited; it is not one maker's specification.

PartRoleFix in the order
Three-phase filter inductorSeries element of the low-pass filter. [1] [2]mH; current; loss.
Filter capacitor bankShunt element, Y-connected in one design. [1]µF; standard.
Terminals or copper barsInput and output connections. [1] [2]Cross-section.
Frame or cabinetMounting; IP00 open frame as standard. [1] [2]IP; cooling.

05

Fill the specification fields with values for your order

An output filter quotation needs values for your drive and motor. The table explains each field, gives published values where a reviewed source states them, and says what to obtain from the supplier.

FieldWhat it means and published valuesAsk the supplier for
Rated Voltage (V AC)e.g. 3 × 690 VAC ±10%; 3 × 380 V ±10%. [1] [2]Voltage.
Rated Current (A)e.g. 13–1,320 A at 45 °C; 3.3–1,209 A. [1] [2]Current; overload.
Inductance (mH)e.g. 11.7 mH at 13 A to 0.12 mH at 1,320 A. [1]Value.
Capacitance (µF)e.g. 4.7 µF at 13 A to 816 µF at 1,320 A. [1]Value; connection.
Cutoff Frequency (kHz)Not stated in the reviewed sources. Minimum switching 1.5–6 kHz. [1] [2]Resonance; min. switching.
Attenuation (dB)Not stated in the reviewed sources. Residual ripple <5%. [1]Ripple; attenuation.
Operating Temperature (°C)e.g. ambient −25 to +40 °C. [2]Range; derating.
Insulation Resistance (MΩ)Not stated in the reviewed sources.Value.
Dielectric Strength (kV)e.g. 3,600 VAC for 1 minute (one test). [1]Test voltages.
Protection Ratinge.g. IP00. [1] [2]IP; enclosure.
Weight (kg)e.g. 14–945 kg; 7–22.5 kg small models. [1] [2]Weight.

06

Send the drive, motor and filter data together

Paste it into your enquiry below or into an email to a maker, then replace every bracket.

Drive: [make; model; control mode]
Supply: [voltage; frequency]
Current: [rated; overload]
Switching: [kHz; fixed]
Motor: [power; frequency range; motors in parallel]
Cable: [length; type; step-up transformer]
Limits: [ripple; voltage drop; losses]
Installation: [IP; cooling; ambient]

See manufacturer records Send an enquiry through CNFX

Find output LC filter manufacturers

These companies list output filter on their own websites.

Cangzhou Hanyang Electrical Appliance Manufacturing Co., Ltd.
Manufacturing site to be confirmed for the order

Its website has a product page for output filter.

Product scope checked 2026-10-12

Product page on own website · profile compiled by CNFX from public sources
Shanghai Jingzhao Electric Co.,Ltd.
Manufacturing site to be confirmed for the order

Its website has a product page for output filter.

Product scope checked 2026-10-12

Product page on own website · profile compiled by CNFX from public sources

Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.

Share this page

Buyer questions

What does a sine wave output filter do?

Schaffner says it converts a drive's rectangular PWM output into a smooth sine wave with low ripple, protecting the motor. [1]

Does the drive need special settings?

Schaffner requires a fixed switching frequency at or above the filter minimum and scalar (V/Hz) mode. [1]

How long can the motor cable be?

Schaffner lists up to 2,000 m for the FN 5040 HV; VEIKONG recommends up to 500 m. [1] [2]

When does a drive need an output filter for long motor cables?

DOE's motor tip sheets say reflected waves are "generally not a problem" under 15 ft, while with modern IGBT drives "cable lengths of 50 feet or more almost always need mitigation" such as load reactors or dV/dt filters. [3]

Why does the switching frequency matter when choosing a sine wave filter for a high-speed motor?

Each filter is listed for a switching frequency and a maximum motor frequency: MTE lists its High Frequency SineWave Guardian models at 2 kHz for 6–200 Hz, 3.5 kHz for 6–240 Hz and 5 kHz for 6–300 Hz system frequency. [4]

Sources and what still needs a direct check

Sources checked 2026-10-12. Schaffner, VEIKONG and MTE Corporation publish datasheets or selection tables for sine wave output filters for motor drives; the US Department of Energy's tip sheets explain why they are fitted.

  1. Schaffner — FN 5040 HV LC sine wave filter datasheet (distributor copy, Astat) ↗ Manufacturer datasheet Return to text ↑
  2. VEIKONG — Sine wave filter datasheet (No. 29092020-SF) ↗ Manufacturer datasheet Return to text ↑
  3. US Department of Energy, Advanced Manufacturing Office — Motor Systems Tip Sheets #14 (When should inverter-duty motors be specified?) and #15 (Minimize adverse motor and ASD interactions), 2012 ↗ Government tip sheet Return to text ↑
  4. MTE Corporation — High Frequency SineWave Guardian filter, model selection table ↗ Manufacturer product page Return to text ↑

Still to check yourself

  • Fix voltage and current.
  • Match switching frequency and drive mode.
  • Check cable length.
  • Set ripple, drop and loss limits.
  • Verify the legal supplier and tests.
Buyer enquiry

Request manufacturing insight for Output Filter (LC Filter)

Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.

Where it goes
Straight to the CNFX editorial desk, and to the manufacturer if this product is linked to a claimed profile. Nothing is broadcast to a supplier list.
Your details stay here
We do not sell or rent enquiry data, and we do not add you to a mailing list. Used only to answer this request.
No commission, no middleman
CNFX is a directory. We take no cut of any order and never negotiate on a supplier's behalf.
What to include
Share your product specifications, quantity, destination and target delivery date.

Your business information is used only to process this request.

Thank you! Your message has been sent. We'll respond within 1–3 business days.
Sorry, we couldn't send your message. Please try again, or email us at [email protected].

Need to Manufacture Output Filter (LC Filter)?

Compare manufacturer profiles with relevant product and process capability.

Previous Product
XY Positioning Stage
Last Product
Get QuotesChat