Editorial Technical Reference

Main circuit breaker (low-voltage air circuit breaker as the incomer of a main switchboard)

Low-voltage air circuit breakers used as the main incomer of a switchboard · Icu, Ics, Icw and Icm, utilization category B for selectivity, ZSI, draw-out cradle positions, padlocking and mechanical interlocks between incomers

The main circuit breaker of a switchboard is the air circuit breaker between the transformer or generator and the busbars. It has to break the full prospective fault current, stay closed long enough for the outgoing breakers to clear their own faults, and come out of its cradle for maintenance without dismantling the board. Specify the short-circuit ratings at the board voltage, the selectivity it must give, and the draw-out and interlocking arrangement.

Low-voltage air circuit breakers (power circuit breakers) used as main incomers and bus couplers of switchboards, fixed or in draw-out cradles, with their short-circuit ratings, selectivity features, cradle positions and incomer interlocks. Miniature circuit breakers are covered on the Low-voltage miniature circuit breakers page; residential smart panels on the Smart home circuit breaker panel page; the switchboards themselves on the Power distribution panel (distribution board, panelboard) page; arc chutes on the Replacement arc chute for low-voltage air circuit breakers page; trip unit electronics on the Control PCB of a circuit breaker trip unit page.

CNFX editorial research · Sources checked October 12, 2026 · 3 sources

Large dark grey air circuit breaker with vented arc chambers and three copper terminal pads at the back, sitting in a steel draw-out cradle with rails and a spring mechanism, in front of an open switchgear cubicle
Air circuit breaker in a draw-out cradle

01

Short-circuit ratings at the switchboard voltage

An incomer is rated four ways for faults: ultimate breaking capacity Icu, service breaking capacity Ics, short-time withstand Icw for a stated time, and making capacity Icm. Himel's HDW3 data sheet for a 6300AF frame, 4,000 A, 3-pole draw-out breaker lists Icu of 120 kA at 400 V and 85 kA at 690 V, Ics of 100 kA at 400 V and 75 kA at 690 V, and Icw of 85 kA at 400 V and 75 kA at 690 V, both for 1 s, with a maximum tripping time of 25 ms. [2] WEG's ABW range brochure gives Ics as 100% of Icu across the range, Icw for 1 s from 42 to 100 kA, for 3 s from 25 to 85 kA, and rated currents from 800 A to 6,300 A, to IEC 60947-2. [1]

Editorial calculation from Himel's figures: Ics is 100 ÷ 120 ≈ 83% of Icu at 400 V and 75 ÷ 85 ≈ 88% at 690 V, so on that breaker the service rating, not the ultimate one, is the figure to compare with a fault level the breaker must clear and keep in service. [2]

WEG notes that above 2,000 m altitude voltage and current derating factors apply, and that above 40 °C ambient the maximum rated current values must be checked. [1]

Give the maker the transformer or generator rating and impedance, the prospective fault current at the board, the board voltage and earthing system, the time the incomer must ride through a downstream fault, and the ambient temperature and altitude.

02

Selectivity: category B, Icw and zone interlocking

WEG lists its ABW breakers as utilization category B with Icw ratings for 1, 2 and 3 s, and its trip units offer LSIG protection and "Protection coordinated by the ZSI (Zone Selective Interlocking)"; maximum opening time is 40 ms and closing 80 ms. [1]

ABB's Emax overview table shows the trade-off. In its column marked L, Icu at 415 V is 130 kA, but Icw for 1 s is 10 kA, the utilisation category (to BS EN 60947-2) is A rather than B, and the break time above Icw is 12 ms instead of 30 ms. The table's column headings are garbled in the PDF, so confirm the frame and version against the current ABB catalogue. [3]

For a main incomer that must hold while feeders clear their faults, ask for category B with an Icw and duration that cover the slowest downstream clearing time, and state whether ZSI wiring to the feeder breakers is wanted.

03

Draw-out cradle positions, padlocking and interlocks between incomers

WEG recommends the withdrawable version "for applications in which the occasional replacement or maintenance should be done as quickly as possible" and describes three positions in the rack: inserted, with power and control circuits connected; test, "position in which only the control circuits are connected"; and withdrawn, with both disconnected. The rack position can be locked by padlock, and cell switches signal each position. [1]

For boards with two incomers or an incomer and a bus coupler, WEG offers a mechanical interlock that "enables two or three circuit breakers to be mechanically interlocked with cables", with 1.6 m cables. [1] Himel's 4,000 A draw-out breaker weighs 233 kg and measures 441.5 mm high, 815 mm wide and 508 mm deep, figures to check against the board's cubicle and lifting arrangements. [2]

04

Main circuit breaker order details

Paste it into your enquiry below or into an email to a maker, then replace every bracket.

Supply: [transformer/generator kVA; impedance; voltage; earthing]
Current: [In; ambient; altitude]
Faults: [prospective kA; Icu; Ics; Icw and duration; Icm]
Selectivity: [category B; ZSI; downstream breakers]
Trip unit: [LSIG; metering; communication]
Mounting: [fixed or draw-out; poles; neutral]
Controls: [motor; closing and shunt coils; undervoltage]
Interlocks: [incomers; bus coupler; padlocks]

See manufacturer records Send an enquiry through CNFX

Main circuit breaker makers

Manufacturer profiles associated with Main Circuit Breaker.

Sourcing Main Circuit Breaker from China?
Tell us your specification and target quantity — we will match it against manufacturer records and come back with the factories that fit.
Request manufacturers We manufacture this

Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.

Share this page

Buyer questions

What is the difference between Icu and Ics?

Icu is the ultimate breaking capacity, Ics the service breaking capacity; Himel's 4,000 A HDW3 lists Icu 120 kA and Ics 100 kA at 400 V. [2]

Why does an incomer need Icw?

Icw is the current it withstands for a set time while staying closed, so outgoing breakers can clear first; WEG lists 1, 2 and 3 s values with utilization category B. [1]

What does the test position do?

In WEG's withdrawable breakers only the control circuits are connected, so the breaker can be operated without connecting the power circuit. [1]

Is a current-limiting version better as a main breaker?

ABB's table shows a version with high Icu but Icw of 10 kA and category A, which limits selectivity; check against the board's needs. [3]

Sources and what still needs a direct check

Sources checked 2026-10-12. WEG publishes a brochure for its ABW and ABWC air circuit breakers; Himel publishes product data sheets for its HDW3 breakers; ABB published an Emax air circuit breaker overview.

  1. WEG — Air circuit breakers ABW/ABWC brochure (50026203) ↗ Maker brochure Return to text ↑
  2. Himel — HDW363M403DHNN56 air circuit breaker HDW3, 6300AF, 4000 A, 3P, drawout, product data sheet ↗ Maker data sheet Return to text ↑
  3. ABB — Emax air circuit breaker overview (electrical specifications) ↗ Maker catalogue page Return to text ↑

Still to check yourself

  • Fix the prospective fault level at the board.
  • Match Icu, Ics, Icw and duration.
  • Choose category B and ZSI as needed.
  • Confirm draw-out positions and padlocking.
  • Specify incomer and coupler interlocks.
  • Verify the legal supplier and factory.
Buyer enquiry

Request manufacturing insight for Main Circuit Breaker

Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.

Where it goes
Straight to the CNFX editorial desk, and to the manufacturer if this product is linked to a claimed profile. Nothing is broadcast to a supplier list.
Your details stay here
We do not sell or rent enquiry data, and we do not add you to a mailing list. Used only to answer this request.
No commission, no middleman
CNFX is a directory. We take no cut of any order and never negotiate on a supplier's behalf.
What to include
Share your product specifications, quantity, destination and target delivery date.

Your business information is used only to process this request.

Thank you! Your message has been sent. We'll respond within 1–3 business days.
Sorry, we couldn't send your message. Please try again, or email us at [email protected].

Need to Manufacture Main Circuit Breaker?

Compare manufacturer profiles with relevant product and process capability.

Previous Product
Load Sharing Controller
Next Product
Main Power Contactor
Get QuotesChat