How much current the outgoing circuits of a cabinet power distribution unit can carry together · rated diversity factor from IEC 61439, the 0.9 to 0.6 table used for switchboard busbars, the 0.8 to 0.5 table for distribution boards, continuous loads over 30 minutes, and the assembly maker's own figure
A power distribution unit takes one supply through a main breaker onto busbars and splits it into outgoing circuits. Outgoing breakers mounted side by side heat each other, and the IET article notes that "it wouldn’t be economical for a manufacturer to rate the full assembly with all outgoing circuits rated at 100 %". The rated diversity factor states how far the circuits can be loaded together, and the buyer has to know which figure applies before sizing the load.
Power distribution units inside control cabinets and small switchboards: incomer, busbars and outgoing protective devices, rated for simultaneous loading of the outgoing circuits. Busbar systems and distribution blocks are covered on the Control-cabinet power distribution unit (busbar system and power distribution blocks) page; distribution boards and panelboards on the Power distribution panel (distribution board, panelboard) page; busbar copper on the Copper busbar page; motor control centres on the Motor control center (MCC) page; smart home panels on the Smart home circuit breaker panel: load-managing residential panel for service-upgrade avoidance page.
Start with your task
01
Joe Cannon, writing in the IET's Wiring Matters (Issue 96, July 2023), quotes BS EN 61439-1:2011's definition of the rated diversity factor: "Per unit value of the rated current, assigned by the assembly manufacturer, to which outgoing circuits of an assembly can be continuously and simultaneously loaded taking into account the mutual thermal influences." A factor of 0.5 on a 32 A circuit, for example, means 16 A. [1]
The article notes that continuous loads are not defined in the BS EN 61439 series, but that the standard warns about loads energised for more than 30 minutes; some manufacturers treat more than 30 minutes as continuous, others more than 1 hour. Electric vehicle charging points and heat pumps are given as sustained loads where the factor matters. [1]
It also quotes BS EN 61439-1: "The rated diversity factor multiplied by the rated current of the circuits shall be equal to or higher than the assumed loading of the outgoing circuits", and notes that a circuit's rating inside an assembly may be lower than the device rating under its own product standard. [1]
List which outgoing circuits carry continuous loads (more than 30 minutes on) and which run together, and ask the assembly maker for the rated diversity factor it assigns and how it was verified.
02
Schneider Electric's Prisma G catalogue (2015) takes the diversity factor into account when sizing busbars and attributes this table to "Standard IEC 61439-1 and 2 §4.7": 0.9 for 2 and 3 circuits, 0.8 for 4 and 5, 0.7 for "6 and 9" (6 to 9) and 0.6 for 10 and more. [2]
The IET article gives a lower table for distribution boards operated by ordinary persons, from BS EN 61439-3:2012 Table 101, and calls it the assumed loading factor, "the maximum permitted rated diversity factor to be applied by the user". In the consumer unit instructions it surveyed, British General, Contactum, Hager and Lewden use Table 101, while Fusebox, Live and MCG recommend a 60% factor where breakers are loaded continuously. [1]
| Outgoing circuits | IEC 61439-1/-2 table cited by Schneider | BS EN 61439-3 Table 101 cited by IET |
|---|---|---|
| 2 and 3 | 0.9 | 0.8 |
| 4 and 5 | 0.8 | 0.7 |
| 6 to 9 | 0.7 | 0.6 |
| 10 and more | 0.6 | 0.5 |
State whether the unit is built as a switchboard assembly (IEC 61439-2) or a distribution board for ordinary persons (IEC 61439-3), and use the maker's assigned factor rather than either table where the maker gives one.
03
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
Supply: [voltage; incomer rating; fault level] Outgoing: [number; device ratings] Loads: [continuous; intermittent; simultaneous] Rating: [RDF assigned; verification] Standard: [IEC 61439-2; -3] Ambient: [temperature; IP of enclosure] Busbar: [current; material]
Manufacturer profiles associated with Power Distribution Unit (PDU).
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
The per-unit share of rated current that outgoing circuits can carry continuously and simultaneously, as assigned by the assembly manufacturer under BS EN 61439-1. [1]
0.6 in the IEC 61439-1/-2 table Schneider cites for busbars; 0.5 in BS EN 61439-3 Table 101 for distribution boards. [2] [1]
The standard does not define them; the IET article notes the 30-minute caution and makers using 30 minutes or 1 hour. [1]
The assembly manufacturer, who agrees it with the designer or states it in installation instructions. [1]
Sources checked 2026-10-13. The IET publishes Wiring Matters (Issue 96, July 2023, article by Joe Cannon); Schneider Electric's Prisma G catalogue 2015 is read from an online flip-book copy.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.