Active power filters · Current rating by voltage, harmonic orders and THDi targets, closed versus open loop, CT placement, response time, losses, derating for temperature and altitude, paralleling
An active power filter (APF) is a power electronic unit, built from current transformers, a digital signal processor and an IGBT inverter with a DC bus, connected in parallel with non-linear loads, that measures the harmonic and reactive current drawn by drives, rectifiers and other loads and injects an opposing current so the supply sees a cleaner, better-balanced waveform. Ask three things first: how much harmonic current must be compensated at which voltage, which harmonic orders and distortion target the site needs, and how the unit is controlled, cooled and derated.
Low-voltage active power filters (active harmonic filters) for three-phase industrial and building systems, wall-mounted, cabinet or module types. Passive harmonic filters, static var generators used only for reactive power, power factor capacitor banks and filter capacitors sold alone are outside this page.
01
Schneider Electric's AccuSine PCS+ specification lists standard RMS output ratings of 60, 120, 200 and 300 A at 380–480 V AC (47–235 A at 480–600 V and 40–200 A at 600–690 V), for three-phase systems with or without neutral, at 50/60 Hz ±3 Hz. It cancels harmonics from the 2nd to the 51st order, each selectable by amplitude and on/off, and also corrects power factor to a set target, leading or lagging. [1]
Its stated attenuation is below 3% THD(i), with up to 20:1 THD(i) reduction, in closed loop when the load harmonic current is above 50% of the unit's rating, and below 5% TDD in open loop. Up to 10 units of any size combination can run in parallel on one set of CTs, with master/master, lead/lag or load-share operation. [1]
Editorial calculation: a 300 A unit at 400 V corresponds to about √3 × 400 × 300 ≈ 208 kVA of compensating capacity; with losses below 3% it dissipates up to about 6.2 kW of heat that the room or cabinet must remove. [1]
Give the supplier the system voltage, frequency and earthing, the loads (drives, rectifiers, UPS, LED) and their harmonic spectrum or measurements, the target THDi, TDD or THDv and the standard it must meet, reactive power and unbalance compensation needs, CT locations and ratios, ambient temperature and altitude, enclosure type, communications and quantities.
02
The AccuSine PCS+ uses an IGBT three-level inverter with digital FFT control. It accepts CTs of any ratio with 1 A or 5 A secondary (two or three for 3-wire systems, three for 4-wire), placed on the source side or load side in closed-loop control for new installations, or in open loop for retrofits. Control response time is 25 µs, harmonic correction takes 2 cycles and reactive correction 1/4 cycle. [1]
Smaller wall-mount units operate from 0 to 45 °C and others 0 to 40 °C, derating 2% per °C up to 50 °C and shutting down if inlet air reaches 51 °C; altitude rating is 1,000 m, derating 1% per 100 m above, to a maximum of 4,800 m. Losses are below 3% at 480 V and below 5% at 690 V, and noise below 70 dB at one metre. It communicates by Modbus RTU and Modbus TCP/IP. [1]
Editorial calculation: at 50 Hz one cycle is 20 ms, so harmonic correction in 2 cycles takes about 40 ms and reactive correction in 1/4 cycle about 5 ms. A unit installed at 2,000 m loses about 10% of output (1,000 m × 1%/100 m), so a 300 A unit would deliver about 270 A. [1]
03
An ABB Review article (4/2010) on PQF active filters explains that in closed-loop systems the CTs measure the current upstream of the load and filter connection, so measurement and other inaccuracies are cancelled, while in open-loop systems the load current is measured and the inverted signal drives the IGBT bridge without feedback. It describes a frequency-domain approach that treats each harmonic and its system characteristics individually, allowing requirements to be preset per harmonic and orders already handled by another device to be left out. [3]
The Hitachi Energy PQF data list closed-loop compensation, filtering programmable per harmonic in amperes, attenuation better than 97% at rated load, reaction time below 0.5 ms, filtering response of two network cycles (10–90%), a cos φ target programmable from 0.6 inductive to 0.6 capacitive, up to 8 units combined (4 for PQFS) in master/master or master/slave arrangement, and load balancing between phases and, on PQFS, between phase and neutral. [2]
The ABB article gives a balancing example in which an unbalanced load drew 49.1, 5.3 and 5.1 A on L1–L3 with 44.1 A in the neutral; with the closed-loop filter balancing, the phases carried 19.6, 19.4 and 19.5 A and the neutral 3.5 A. It also lists reasons passive filters fit dynamic LV installations less well, among them overcompensation with loads whose cos φ is already high and efficiency that depends on network impedance. [3]
Editorial calculation: the mean of the unbalanced phase currents is (49.1 + 5.3 + 5.1) / 3 ≈ 19.8 A, close to the balanced 19.5 A per phase, and the neutral current fell by 1 − 3.5 / 44.1 ≈ 92%. Harmonic ranges differ by maker (2nd–50th here, 2nd–51st in the AccuSine data above), so list the orders your measurements show. [3] [2] [1]
| Hitachi Energy PQF data | PQFI | PQFM | PQFS |
|---|---|---|---|
| Connection | 3-wire | 3-wire | 3-wire / 4-wire |
| Network voltage | 208–480 V; 480–690 V | 208–480 V; 480–690 V (600 V for cULus) | 208–240 V; 380–415 V |
| Line current rating | 300–450 A; 180–320 A | 70, 100, 130, 150 A; 100 A | 30 to 120 A in eight steps |
| Selectable orders (2nd–50th) | 20 | 20 | 20 (3-wire), 15 (4-wire) |
State closed or open loop and CT position, the orders to be filtered and their limits, whether load balancing (phase and neutral) and reactive compensation are needed, and redundancy for paralleled units.
04
A 2025 open-access study in Scientific Reports by researchers at Van Lang University and VSB–Technical University of Ostrava connected a shunt active power filter (SAPF) in parallel with an induction hardening (quenching) machine and measured the supply before and after. It reports that current THD fell from 36.35% to 5.21% and power factor rose from 0.89 to 0.98; the fluctuation of what the authors call the sintering temperature narrowed from ±50 °C to ±5 °C and the defective product rate dropped from 90% to 1%, with hardness held at 58–62 HRC and hardening depth at 1.8–2.2 mm. [4]
The authors state that when THDi exceeds 12%, high-order harmonics can degrade induction coil performance and cause over- or under-heating, and they set a target of THD below 5% with reference to IEEE 519:2022 and cos φ above 0.9. Each parameter was measured at three different times in the test group. [4]
Editorial calculation: a fall in THDi from 36.35% to 5.21% removes about 86% of the harmonic current relative to the fundamental ((36.35 − 5.21) ÷ 36.35). The measured 5.21% sits just above the authors' own 5% target, which is why an order should state the THD limit, the measuring point (source side or load side), the load condition and the measurement method that acceptance will use, alongside the filter's own published attenuation figure such as the below-3% THD(i) closed-loop figure Schneider gives for the AccuSine PCS+. [4] [1]
05
Suppliers linked to this page list active power filters; each card links to the page reviewed.
Listings include cabinet and module active power filters, hybrid active filters and active harmonic filters alongside static var generators.
06
This is a functional reference built from the sources cited; it is not one maker's design.
| Part | Role | Fix in the order |
|---|---|---|
| Current transformers | Measure load or source current. [1] | Ratio, location, quantity. |
| DSP control | FFT and current reference; per-harmonic frequency-domain control. [1] [3] | Orders and targets. |
| IGBT inverter | Injects compensating current. [1] | Topology and rating. |
| Cooling | Removes losses. [1] | Ambient and derating. |
| Communications | Monitoring and control. [1] | Protocols. |
| Enclosure | Protection and mounting. [1] | IP or UL type. |
07
An active power filter quotation needs values for your system. The table explains each field, gives published values where a reviewed source states them, and says what to obtain from the supplier.
| Field | What it means and published values | Ask the supplier for |
|---|---|---|
| Rated current (A) | 60–300 A at 380–480 V in one range [1]; 30–450 A across another. [2] | RMS output rating. |
| Voltage (V AC) | 380–690 V, +10%/−15%. [1] | Voltage and tolerance. |
| Harmonic orders | 2nd to 51st, selectable [1]; 2nd to 50th, 15–20 selectable. [2] | Orders and limits. |
| THDi target (%) | < 3% closed loop; < 5% TDD open loop. [1] | Guaranteed result and conditions. |
| Response time | 25 µs control; 2 cycles harmonic [1]; < 0.5 ms reaction, 2 cycles filtering. [2] | Response times. |
| Losses (%) | < 3% at 480 V. [1] | Losses at rating. |
| Operating temperature (°C) | 0–40/45 °C, derate 2%/°C to 50 °C. [1] | Range and derating. |
| Altitude (m) | 1,000 m; −1%/100 m above. [1] | Derating. |
| Parallel units | Up to 10 per CT set [1]; up to 8 (4 for PQFS). [2] | Paralleling. |
| Communications | Modbus RTU, Modbus TCP/IP. [1] | Protocols. |
| Load balancing | Phase and neutral balancing on 4-wire units. [2] [3] | Balancing modes. |
08
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
System: [voltage; frequency; earthing] Loads: [type; harmonic spectrum; measurements] Target: [THDi; TDD; THDv; standard] Control: [CT location; ratio; closed or open loop] Site: [ambient; altitude; enclosure] Supply: [communications; paralleling; quantity]
These companies list active power filters.
Lists active power filters (P5 and PRO series) among power quality products.
Product scope checked 2026-10-11
Lists active power filters and static var generators among power quality management products.
Product scope checked 2026-10-11
Lists active power filters (APF) among power quality products.
Product scope checked 2026-10-11
Lists the BY91 series active power filter among APF, SVG and hybrid cabinets and modules.
Product scope checked 2026-10-11
Lists active harmonic filters, static var generators and dynamic voltage regulators.
Product scope checked 2026-10-11
Lists active harmonic filters among static var generators and power factor correction panels.
Product scope checked 2026-10-11
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
Schneider's AccuSine PCS+ cancels the 2nd to the 51st order, each selectable. [1]
The AccuSine PCS+ lists 25 µs control response, 2 cycles for harmonic and 1/4 cycle for reactive correction. [1]
Yes; the AccuSine PCS+ derates 1% per 100 m above 1,000 m, to a maximum of 4,800 m. [1]
Closed-loop units measure current upstream of the load and filter and correct their own errors; open-loop units measure the load current and have no feedback. [3]
Yes; in a published example phase currents of 49.1, 5.3 and 5.1 A became 19.6, 19.4 and 19.5 A, and the neutral fell from 44.1 A to 3.5 A. [3]
In a 2025 Scientific Reports case on an induction hardening machine, a shunt active power filter cut current THD from 36.35% to 5.21% and raised power factor from 0.89 to 0.98. [4]
Sources checked 2026-10-11. Schneider Electric publishes specifications for its own active filter; Hitachi Energy and an ABB Review article describe PQF filters; a 2025 Scientific Reports paper gives before-and-after measurements on one industrial load. Performance for your system must come from the supplier's design study and site measurements.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.