Low-voltage AC transient protection at an identified network connection
A low-voltage AC surge protective device limits transient voltage at an electrical installation. Select it for the actual network configuration, installation point and protective-device arrangement. Surge-current capacity, voltage protection and short-circuit behavior describe different tests.
Low-voltage AC surge protective devices for service entrances, distribution or branch panels and equipment, including products classified under the applicable UL or IEC scheme. Medium-voltage line/station arresters, PV/DC-only devices, data-line protectors and arrester test equipment are outside this page.
Start with your task
01
Raycap’s reference guide distinguishes RSE stacked-MOV products from Strikesorb-based Rayvoss systems. Its application table identifies model-specific test and installation arrangements; the technologies and listed ratings must not be transferred across the whole range. [1]
The RSE Series 1 sheet separately lists maximum surge current of 25–50 kA per mode, UL nominal discharge current of 20 kA and short-circuit current rating of 200 kA. These are not alternative names for the same current capacity. Its UL type designation is Type 1 and Type 2; apply the product’s installation listing rather than assuming UL type labels and IEC test classes are interchangeable. [2]
The guide labels its surge ratings by mode/phase. Compare like-labelled quantities rather than adding protection modes or doubling a per-mode figure to claim a new tested rating. Its short-circuit table footnote also refers to an appropriately rated breaker for the marked arrangements. [1]
02
Raycap’s RSE Series 1 sheet gives different voltage-protection ratings by system and mode. For 480Y/277 V, it lists 1,200 V for L-N, L-G and N-G, 2,000 V for L-L, and MCOV 320 V. Those figures belong to that configuration; they do not specify a delta-system connection or the correct device for every network. [2]
The DEHNguard DG M TNS 275 sheet identifies a Type 2/IEC Class II device for 230/400 V TN-S: Uc 275 V, In 20 kA and Imax 40 kA using 8/20 µs current, and Up ≤ 1.25 kV. The separate Up ≤ 1 kV entry is at 5 kA and must retain that test-current qualifier. [3]
Nominal-voltage ratios are not a method of deriving compatibility or protective performance. Confirm the continuous-voltage rating, protection modes, temporary-overvoltage behavior and connection instructions for the actual earthing and supply arrangement.
03
CITEL’s parameter guide distinguishes continuous operating voltage Uc, protection level Up, nominal discharge current In, maximum discharge current Imax, impulse current Iimp and short-circuit rating Isccr. A product’s kA figure is incomplete without identifying which quantity and test it represents. [4]
These laboratory test descriptions do not establish survival of an equal number of real lightning strikes. Real surge exposure and the installed assembly are not established by multiplying a declared current by the number of test strokes.
CITEL’s Protection Kit page labels the assembly Type 1+2 and prints a 12.5 kA @ 8/20 µs figure. Its parameter page defines Iimp with 10/350 µs. Do not relabel the kit-page figure as Iimp; obtain the exact model data sheet and confirmation of the declared current and waveform from CITEL. [5] [4]
| Parameter | CITEL’s documented test distinction |
|---|---|
| In | Repetitive 8/20 µs withstand test; the summary specifies 15 strokes. [4] |
| Imax | Type 2 maximum withstand for a single 8/20 µs test stroke. [4] |
| Iimp | Type 1 withstand defined using a 10/350 µs test stroke. [4] |
| Isccr | SPD and associated disconnecting device tested together for the declared short-circuit condition. [4] |
04
CITEL describes kits combining an SPD with a specific fuse and busbar, and says the external fuse is declared by the SPD manufacturer. Selection includes the disconnection arrangement, not just the plug-in protection module. [5]
The DEHN sheet lists maximum mains-side protection of 125 A gL/gG and short-circuit withstand of 50 kArms with the specified maximum mains-side protection. Preserve that pairing; the fuse value is not a universal breaker recommendation and the short-circuit value is not an impulse-current rating. [3]
Identify the available fault current, declared backup protection, installed conductor arrangement and the complete product’s instructions. Obtain the relevant test/listing documentation for the offered model and the local installation requirements.
05
The RSE Series 1 sheet separates protection modes, thermal protection, status indication and optional alarms or contacts. Confirm the ordered options, rather than treating every monitoring function as standard. [2]
| Assembly boundary | Information to obtain |
|---|---|
| Protection element and disconnection | Identified module, thermal/end-of-life behavior and declared backup protection. [2] [5] |
| Network connection | System voltage/earthing, modes, installed conductors and connection instructions. |
| Status and remote indication | Supplied indication, alarm/contact options and interpretation of a failed or unpowered indication. [2] |
| Enclosure | Protection of the complete installation, including connections; use the identified model’s enclosure specification. |
06
Require the model and its declared test basis beside each rating.
| Order field | Required definition |
|---|---|
| Application | AC system voltage/configuration, earthing and installation point. |
| Current ratings | In/Imax/Iimp or the applicable declared rating, waveform and per-mode/per-phase basis. [4] [1] |
| Voltage protection | Uc/MCOV and Up/VPR for the stated mode and test; do not merge values from different modes. [3] [2] |
| Fault protection | Available fault current and manufacturer-declared fuse/breaker combination. [5] |
| Installed package | Mounting, connections, enclosure, status and remote contacts supplied. |
07
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
System: [voltage; configuration; earthing] Location: [service entrance, distribution, branch, equipment] Ratings: [type/class; In; Imax per mode; Up; Uc; SCCR] Connection: [parallel or in-line; conductor; breaker or fuse] Enclosure: [DIN rail or panel; IP/NEMA] Monitoring: [LED; alarm; dry contact; SNMP] Standard: [UL 1449 or IEC 61643-11]
13 companies list this product among what they make. Company figures are quoted from each company's own website; every card states where the relationship came from.
Lists low-voltage AC SPDs as well as a separate DC range.
Product scope checked 2026-10-18
Lists an AC T1+T2 surge protection device within its SPD range.
Product scope checked 2026-10-18
Lists modular surge protective devices within its building-protection range.
Product scope checked 2026-10-18
Lists low-voltage lightning arresters; obtain the applicable model classification and test documentation.
Product scope checked 2026-10-18
Lists surge protection devices in its low-voltage product range.
Product scope checked 2026-10-18
Lists low-voltage surge protection devices separately from its solar SPD products.
Product scope checked 2026-10-18
Lists AC and DC SPD variants and distinguishes their application.
Product scope checked 2026-10-18
Lists AC SPDs separately from DC photovoltaic SPDs.
Product scope checked 2026-10-18
Lists AC SPD types separately from DC and signal surge protection.
Product scope checked 2026-10-18
Lists AC DIN-rail and panel SPDs with separate IEC and UL product ranges.
Product scope checked 2026-10-18
Lists SPDs among its low-voltage distribution products.
Product scope checked 2026-10-18
Lists three-phase surge protection devices for electrical installations.
Product scope checked 2026-10-18
Lists low-voltage AC SPD products within its SPD/arrester range.
Product scope checked 2026-10-18
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
No. Raycap lists maximum surge current, nominal discharge current and SCCR separately. Preserve the quantity, waveform and connection/test basis with each figure. [2]
CITEL describes a defined laboratory waveform and repetition test. It does not establish the number of real lightning events the installed device will survive. [4]
Sources checked 2026-10-18. Original Raycap product documents, the identified DEHN sheet and CITEL technical pages. Product ratings and test summaries do not create a shared installation rule or a lightning-strike lifetime guarantee.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.