Instrument voltage transformers for grids · Accuracy class and burden, rated voltage factor, single- or double-pole insulation, ferroresonance and open-delta damping, insulation levels
A voltage transformer, or potential transformer, steps a line voltage down to a standard secondary value such as 100/√3 V so meters and protection relays can measure it while staying isolated from the high-voltage circuit. Ask three things first: the accuracy class and burden the meters and relays need; how the network is grounded, since that sets single- or double-pole insulation and the rated voltage factor; and how ferroresonance will be prevented on ungrounded systems.
Inductive instrument voltage transformers for medium-voltage grids, switchgear and generation, single- or double-pole insulated, with reference to high-voltage inductive and capacitive types. Isolated electronic voltage sensors, power and distribution transformers, and capacitive voltage indicators are outside this page except where compared.
01
RITZ's medium-voltage instrument transformer catalogue defines limits for voltage error and phase displacement that must hold between 80% and 120% of rated voltage with burdens from 25% to 100% of rated burden at power factor 0.8: class 0.2 allows ±0.2% and ±10 minutes, class 0.5 ±0.5% and ±20 minutes, and class 1 ±1% and ±40 minutes. It states that "in single pole insulated transformers, it is common practice to use a rated voltage factor of 1,9 x the rated voltage for a load duration of 8 hours", and 1.2 × for all other types. [1]
Its VES indoor single-pole VTs for 12, 17.5 and 24 kV take primary voltages from 10,000/√3 to 22,000/√3 V, give 100/√3 or 110/√3 V secondaries plus 100/3 or 110/3 V earthing windings, and are rated 20 VA in class 0.2, 50 VA in class 0.5 and 100 VA in class 1, with a 6 A thermal limit current also at 1.9 × Un for 8 hours. A VT can only be reconnected to another primary voltage by secondary tapping; the class stays the same but the rated burden falls by roughly the square of the voltage reduction. [1]
Editorial calculation: a 10,000/√3 V primary is about 5,774 V phase to earth, so 1.9 × for 8 hours is about 10,970 V — close to full line voltage, which a phase-to-earth VT can see during an earth fault on an ungrounded network. [1] [2] A 100/√3 V secondary is about 57.7 V and a 100/3 V earthing winding about 33.3 V; halving the primary voltage by tapping would cut a 50 VA rated burden to about 12.5 VA. [1]
Give the supplier the highest voltage for equipment and insulation level, rated primary and secondary voltages, single- or double-pole insulation, network grounding and rated voltage factor, the number of secondary windings with class and burden for each (metering and protection), any residual (open-delta) winding and its thermal output, frequency, indoor or outdoor installation and altitude, fuse or touch-proof design, partial discharge limits, mounting dimensions, and quantity.
02
RITZ warns that a VT must never be short-circuited on its secondary side, that the grounded "N" end of a single-pole VT's primary must not be removed in service, and that in a V-connection of two double-pole VTs only one transformer's secondary may be grounded. Ferroresonance can occur with single-pole VTs on an ungrounded (insulated neutral) network after switching surges: the earth capacitance and VT inductance oscillate, the core saturates and overheats, and the resin body can flash over and burst. A residual winding in open delta with a damping resistor, reactor or both prevents this, provided the open delta is grounded only once. [1]
RITZ's damping-unit note explains that in three-phase ferroresonance the open-delta voltage is about 70 to 90% of phase-to-earth voltage at roughly half the system frequency, and that the damping load must still let the network run with an earth fault for 8 hours without exceeding the residual winding's thermal limit. For a winding rated 6 A, a damping resistor at 110 V must not be below 20 Ω, which limits its damping power; a reactor that saturates during ferroresonance drops to about 1 Ω and damps far harder but less so at small amplitudes, so RITZ combines both. [2]
RITZ's insulation table pairs 12 kV equipment with 28 kV power-frequency and 75 kV lightning-impulse withstand, 24 kV with 50 and 125 kV, and 36 kV with 70 and 170 kV, and gives the example that a 75 kV BIL at 2,500 m altitude must be raised to 90 kV. Partial discharge is tested above 3.6 kV rated voltage, at 1.2 × Um/√3 with a 20 pC limit for single-pole VTs and 1.2 × Um with 20 pC for double-pole VTs; indoor units are designed for −5 to +40 °C. [1]
03
Arteche lists medium-voltage VTs for primary and secondary air-insulated switchgear, generation and capacitor banks, including support types up to 72.5 kV, fused support types up to 36 kV, touch-proof types up to 52 kV, and units supplying auxiliary power up to 3 kVA. [3] At transmission level Trench lists eco-fluid inductive VTs up to 550 kV with hermetic bellows [4] and capacitive VTs up to 1,200 kV that also couple power-line carrier and damp ferroresonance. [5]
Suppliers linked to this page list cast-resin indoor and outdoor voltage transformers, low-voltage VTs, fused VTs and metering units; ask each for the class and burden per winding, rated voltage factor, insulation level and test reports, and ferroresonance damping options.
04
This is a functional reference built from the sources cited; it is not one maker's specification.
| Element | Role | Fix in the order |
|---|---|---|
| Iron core | Single magnetic core carrying the windings. [1] | Saturation margin. |
| Primary winding | High-voltage winding, grounded N end on single-pole VTs. [1] | Rated primary voltage. |
| Secondary windings | Metering, protection and residual windings. [1] | Class and burden each. |
| Resin or fluid insulation | Cast resin (MV) or paper-fluid (HV). [1] [4] | Insulation level. |
| Terminal box | Sealable box; each terminal can be grounded. [1] | Terminals and fuses. |
| Damping device | Resistor and/or reactor on open delta. [1] [2] | Thermal rating. |
05
A voltage transformer quotation needs values for your network. The table explains each field, gives published values where a reviewed source states them, and says what to obtain from the supplier.
| Field | What it means and published values | Ask the supplier for |
|---|---|---|
| Rated primary voltage (kV) | e.g. 10,000/√3 to 22,000/√3 V (VES). [1] | Primary and taps. |
| Rated secondary voltage (V) | 100/√3 or 110/√3 V. [1] | Secondary per winding. |
| Accuracy class | 0.2, 0.5, 1 (±0.2, ±0.5, ±1%). [1] | Class per winding. |
| Rated burden (VA) | 20/50/100 VA in class 0.2/0.5/1 (VES). [1] | Burden per winding. |
| Frequency (Hz) | 50 or 60 Hz. [1] | Frequency. |
| Insulation level (kV) | 12 kV: 28 kV power-frequency, 75 kV impulse. [1] | Levels and altitude. |
| Operating temperature (°C) | Indoor −5 to +40 °C. [1] | Range. |
| Degree of protection | Indoor or outdoor design. [1] | Rating. |
| Rated short-time thermal current (kA) | Defined for CTs; VTs give thermal limit current, 6 A (VES). [1] | Thermal limit. |
| Rated dynamic current (kA) | CT rating; not a VT rating in the reviewed source. [1] | Fuse breaking capacity if fused. |
| Weight (kg) | 19–27 kg (VES 12–24). [1] | Weight. |
| Insulation medium | Cast resin; paper with fluid for HV. [1] [4] | Medium. |
06
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
Network: [Um; insulation level; frequency; grounding] Voltages: [primary; secondary; taps] Windings: [class and burden each; residual winding] Voltage factor: [1.2 continuous; 1.9 × 8 h] Ferroresonance: [damping device] Installation: [indoor/outdoor; altitude; fused or touch-proof] Tests: [type and routine; partial discharge]
These companies list voltage or potential transformers.
Lists 0.66–1 kV cast-resin voltage transformers and current transformers.
Product scope checked 2026-10-11
Lists potential transformers among instrument and power transformers.
Product scope checked 2026-10-11
Lists indoor cast-resin PTs for 3–10 kV and CT-PT metering units.
Product scope checked 2026-10-11
Lists voltage transformers with circuit breakers and switches.
Product scope checked 2026-10-11
Lists voltage transformers among precision measurement products.
Product scope checked 2026-10-11
Lists indoor and outdoor voltage transformers.
Product scope checked 2026-10-11
Lists voltage transformers among electrical products.
Product scope checked 2026-10-11
Lists voltage transformers with substations and switchgear.
Product scope checked 2026-10-11
Lists medium-voltage potential transformers and fused voltage transformers.
Product scope checked 2026-10-11
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
RITZ gives class 0.5 limits of ±0.5% voltage error and ±20 minutes phase displacement between 80% and 120% of rated voltage at 25–100% of rated burden. [1]
RITZ says that for single-pole insulated VTs "it is common practice to use a rated voltage factor of 1,9 x the rated voltage for a load duration of 8 hours", and 1.2 × for other types. [1]
Sources checked 2026-10-12. RITZ, Arteche and Trench all make instrument transformers and describe their own ranges; RITZ's catalogue cites the IEC 60044 series; the standard edition named in the buyer's specification and the network study should govern a purchase.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.