PLC chassis networking · Ethernet communication modules that plug into a modular controller's backplane: connection counts, packet rates, backplane current and port variants
In a modular PLC the CPU does not have to carry every network port itself. A communication interface module takes one slot in the controller's chassis or on its mounting rail, draws its power from the backplane bus, and adds Ethernet ports through which the controller exchanges I/O data with remote stations and drives, serves HMIs and messages, and routes traffic between networks. What separates one module from another is less the RJ45 socket than the numbers behind it: how many connections it holds open, how many packets per second it moves, how much backplane current it takes from the rack's power budget, and whether its ports support ring or parallel redundancy.
Plug-in communication interface modules and communication processors for modular PLC chassis and rails, the kind that take a slot beside the CPU and connect it to Ethernet-based networks, with their connection and packet limits, backplane power, ports and redundancy variants. Stand-alone RS-232/422/485 interface hardware is covered on the Serial communication interface page, embedded fieldbus and Ethernet-APL modules for instruments on the Communication module for wired industrial networks page, and stand-alone protocol converters on the Fieldbus gateway page; board-level design of interface cards (PHY, SFP cages, isolated transceivers) is on the Communication interface board page, and CPU modules on the PLC CPU module (processor unit) page. Network switches, IoT gateways and the PLC CPUs themselves are outside this page.
01
Rockwell Automation lists 128 TCP connections and 256 CIP connections for the 1756-EN2T, -EN2TP, -EN2TR and -EN3TR EtherNet/IP modules, with 128 + 128 unconnected messages split between backplane and Ethernet; the newer 1756-EN4TR raises this to 512 TCP connections, 1000 CIP I/O connections and 528 CIP messaging connections. Rockwell adds that the CIP connections can be used in any combination of explicit and implicit traffic. [1]
Packet rate depends on firmware as well as hardware. The same 1756-EN2T is rated at 10,000 I/O packets per second on 2.x firmware and 25,000 on firmware 3.6 or later, with 2000 packets per second for HMI and messaging; the 1756-EN4TR moves 50,000 I/O packets per second without CIP Security, 25,000 with integrity and 15,000 with integrity and confidentiality. Rockwell's footnote matters for sizing: the I/O figures are maximums that assume no HMI or messaging load, the HMI figures assume no I/O, and packet rates vary with packet size. [1]
Siemens states the limits for its CP 1543-1, a communication processor for the S7-1500, as a maximum of 118 connections for open communication through T blocks and 118 for S7 communication, both "abhängig von der Systemobergrenze" (depending on the system upper limit), with 118 active connections in multi-protocol operation. IT services have their own ceilings: 32 FTP client and 16 FTP server connections, 4 HTTP server connections and 1 e-mail client. [2]
Editorial calculation: a controller exchanging I/O with 40 remote stations, each at a requested packet interval of 10 ms in both directions, would need about 40 × 2 × 100 = 8,000 packets per second, inside the 10,000 rated for an EN2T on 2.x firmware but with little margin left. The station count and interval are assumptions for illustration; Rockwell points to its Troubleshoot EtherNet/IP application technique, ENET-AT003, for more detail. [1]
Before choosing a module, list the remote I/O stations, drives, HMIs and peer controllers it must reach, the update interval each needs, and whether any messaging or web traffic shares the same module.
02
A chassis module takes its power from the rack, so it counts against the power supply's budget. Rockwell gives the 1756-EN2T, -EN2TP, -EN2TR and -EN3TR as 1 A at 5.1 V DC and 3 mA at 24 V DC, with 5.1 W dissipation; the fibre 1756-EN2F and the 1756-EN4TR draw 1.2 A at 5.1 V, dissipating 6.2 W and 6.12 W. [1] Siemens' CP 1543-1 is supplied at 15 V DC from the backplane bus and takes 0.35 A (typ.), with a power loss of 5.3 W. [2]
Editorial calculation: 1 A × 5.1 V = 5.1 W for the EN2T and 0.35 A × 15 V ≈ 5.3 W for the CP 1543-1, so in both data sheets the stated dissipation matches the power taken from the backplane. Two EN2T modules in one chassis would add 2 A to the 5.1 V load. [1] [2]
Isolation between the network side and the backplane is basic insulation for a low working voltage. Rockwell rates the EN2T family at 30 V continuous between Ethernet and backplane, USB and backplane, and USB and Ethernet, type tested at 980 V AC for 60 s to IEC/UL 61010-1, while the 1756-EN4TR is type tested at 860 V AC for 60 s. The USB port is for temporary local programming only and is not to be used in hazardous locations. [1]
03
| Variant | Ports and network features | Source |
|---|---|---|
| 1756-EN2F | 1 multimode fibre port with LC connector; 100 Mbps, no auto-negotiation; launch power min. −19 dBm into 62.5/125 µm fibre | Rockwell [1] |
| 1756-EN2T | 2 RJ45 Category 5 ports; 10/100 Mbps | Rockwell [1] |
| 1756-EN2TR, -EN3TR | 2 RJ45 ports; Device Level Ring (DLR) and linear topologies; up to 8 and up to 128 motion axes | Rockwell [1] |
| 1756-EN2TP | Parallel Redundancy Protocol (PRP) | Rockwell [1] |
| 1756-EN4TR | 2 RJ45 Category 5E ports; 10/100 Mbps and 1 Gbps; DLR; PRP from firmware 4.001; up to 256 axes | Rockwell [1] |
| XT versions | Operation from −25 to +70 °C | Rockwell [1] |
| CP 1543-1 | 1 RJ45 port, 10 to 1000 Mbit/s; stateful-inspection firewall; IPsec VPN with up to 16 connections; static IP routing up to 1 Mbit/s | Siemens [2] |
04
The module has to physically fit the rack and be accepted by the CPU. Rockwell's EtherNet/IP modules are one slot wide, can sit in any slot of the 1756-A4, -A7, -A10, -A13 and -A17 chassis, and are open-style with no enclosure rating. [1]
Siemens gives the CP 1543-1 as a single-width S7-1500 module, 35 mm wide, 142 mm high and 129 mm deep, 0.35 kg, IP20, for S7-1500 rail mounting, with up to 8 modules per CPU depending on the CPU type. Its permitted ambient temperature is 0 to 40 °C when installed vertically and 0 to 60 °C when installed horizontally. [2]
Mitsubishi Electric's fact sheet for the MELSEC iQ-R RJ71EN71(C) Ethernet module gives 27.8 mm width, 98 (106) mm height, 110 mm depth and 0.17 kg; the C suffix is listed as a coated version. [3]
05
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
PLC platform: [family; CPU model; firmware] Chassis: [slots free; power supply model; backplane current available] Network: [EtherNet/IP / PROFINET / S7 / Modbus TCP; speed; copper or fibre] Load: [remote stations; drives; HMIs; update intervals] Redundancy: [none / DLR / PRP] Environment: [ambient range; coating; hazardous-area marking]
Manufacturer profiles associated with Communication Interface Module.
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
Rockwell lists 128 TCP and 256 CIP connections for the 1756-EN2T and 512 TCP for the 1756-EN4TR; Siemens lists up to 118 for the CP 1543-1, depending on the system upper limit. [1] [2]
The 1756-EN2T draws 1 A at 5.1 V DC (5.1 W); the CP 1543-1 takes 0.35 A (typ.) at 15 V from the backplane bus (5.3 W). [1] [2]
Yes, in Rockwell's data the 1756-EN2T goes from 10,000 I/O packets per second on 2.x firmware to 25,000 on 3.6 or later. [1]
Sources checked 2026-10-17. Rockwell Automation's 1756-TD003 technical data, a Siemens data sheet for the CP 1543-1 and a Mitsubishi Electric material fact sheet for the RJ71EN71(C) are the manufacturer documents reviewed.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.