Main transformer of a rectifier supply · two valve windings 30° apart for 12-pulse, matched leakage inductance, rectifier load class and IEEE C57.18.10 scope
The main transformer of a rectifier power supply converts the network voltage to the valve-side voltage that the diode or thyristor bridges need, isolates the DC system from the AC network and, with two secondary windings displaced by 30°, lets two six-pulse bridges work as a twelve-pulse rectifier. It is built for converter loads, not as a general distribution transformer. Ask three things first: the pulse number and vector arrangement of the valve windings, the valve-side voltage and current for the DC output required, and the rectifier's overload class that the transformer must also carry.
Converter (rectifier) main transformers feeding semiconductor rectifiers for DC traction substations, electrolysis, DC drives and similar dedicated loads: three-winding units with two valve windings, pairs of double-winding units, and phase-shifting arrangements for 12-pulse and higher pulse numbers, dry-type or liquid-immersed. Liquid-immersed and dry-type distribution and power transformers for general utility, industrial and commercial supplies are covered on the Power transformer page. HVDC converter transformers, furnace transformers and instrument transformers are outside this page.
01
KONČAR's KONRECT 3000A-12P traction rectifier is fed from either a three-phase, triple-winding rectifier transformer with two secondary windings, or two identical three-phase, double-winding rectifier transformers; it therefore has two three-phase inputs requiring a 30° electrical phase shift between them, and its dual full-wave diode bridge produces a 12-pulse DC output. [1]
Ladislav Mlynařík and Jaroslav Novák of the University of Pardubice describe a 3 kV DC Czech railway traction rectifier fed by a 22 kV/3 kV twelve-pulse transformer with two secondary windings, one in delta and one in star, and state that both sections must have the same line voltage and leakage inductance. In their model the transformer's line voltage is 2,500 V, and an air choke of 4 mH follows the rectifier. [2]
They explain that twelve-pulse rectification gives a smoother output voltage than six-pulse and that the 5th, 7th, 17th and 19th harmonics of primary current in the two sections are in phase opposition, so the lowest harmonic frequency on the transformer primary is 550 Hz. [2] Editorial calculation: 550 Hz ÷ 50 Hz = the 11th harmonic.
Editorial note: because cancellation depends on the two valve windings being matched, ask the supplier for measured voltage ratio, phase displacement and short-circuit impedance of each valve winding, not only the transformer's overall values.
Send the network voltage and frequency, pulse number, rectifier type (diode or thyristor), DC voltage and current, valve-side voltage per winding, vector group, rectifier load class, cooling, dry-type or liquid-immersed construction, enclosure, installation altitude and ambient temperature, and the standards to be met.
02
The same KONČAR rectifier takes 2 × 518 VAC / 650 VAC three-phase input at 50 Hz with ±10% tolerance and a nominal 2 × 1,115 A, and delivers 660 V DC nominal (600 V at full load, 750 V at no load), 2,000 kW and 3,000 A. Its load class V allows 1.5 × IN for 2 h and 2 × IN for 1 min, that is 4,500 A for 2 h and 6,000 A for 1 min, and it lists HRN EN 60146 and HRN EN 62590. [1] The datasheet does not say which of the two input voltages applies to which arrangement; confirm the valve-side voltage with the rectifier maker.
IEEE C57.18.10-2021 sets practices and requirements for semiconductor power rectifier transformers for dedicated loads rated 100 kW and above, single-phase or three-phase. It excludes static precipitators, high-voltage converters for DC transmission, other nonlinear loads, and mixed loads with more than 10% non-converter fundamental-frequency power. It specifies routine tests, and an informative annex gives examples of load loss calculations for transformers subjected to nonsinusoidal currents. [3]
Editorial note: a transformer sized only for the rectifier's nominal current may not carry its overload class; state the load class and the harmonic current spectrum in the enquiry so that load losses and temperature rise are calculated for converter current, as the IEEE annex describes.
03
KONČAR accepts either arrangement for its 12-pulse rectifier; the Pardubice railway case uses the three-winding form with one delta and one star valve winding.
| Arrangement | What the source says | Ask the supplier for |
|---|---|---|
| One three-winding transformer | Two secondary windings feed two bridges 30° apart. [1] | Vector group and phase displacement. |
| Two double-winding transformers | Two identical units with a 30° shift between them. [1] | Matching of the two units. |
| Delta and star valve windings | One secondary in delta, one in star; same line voltage and leakage inductance. [2] | Measured ratio and impedance per winding. |
| Six-pulse supply | One bridge; output less smooth than 12-pulse. [2] | Harmonic limits at the connection point. |
04
In KONČAR's substation description the MV circuit breaker energizes the rectifier transformers, whose valve-side busbars enter the rectifier cabinet from below or above; each part along that path has its own order item.
| Component | Role | Fix in the order |
|---|---|---|
| Line (primary) winding | Takes network voltage, e.g. 22 kV. [2] | Voltage, taps, BIL. |
| Valve (secondary) windings | Two windings 30° apart for 12-pulse. [1] | Voltage, current, vector group. |
| Core | Magnetic circuit; magnetizing losses treated as minimal in the Pardubice model. [2] | Core material and no-load loss. |
| Valve-side busbars | Connect to the rectifier feeder busbars, top or bottom. [1] | Terminal position and rating. |
| Cooling and enclosure | Removes the load losses that IEEE C57.18.10 calculates for nonsinusoidal current. [3] | Cooling class and enclosure. |
| Protection interface | MV breaker energizes and protects the set. [1] | Sensors and trips required. |
05
Each rating below has to be stated for the rectifier duty: the IEEE annex calculates load loss for nonsinusoidal current, and the KONČAR load class adds 1.5 × IN for 2 h. Published values appear where a reviewed source gives them.
| Field | What it means and published values | Ask the supplier for |
|---|---|---|
| Rated power (kVA) | IEEE C57.18.10 covers 100 kW and above. [3] | Rating at converter current. |
| Primary voltage (kV) | 22 kV in the Pardubice example. [2] | Voltage and tap range. |
| Secondary voltage (kV) | 2.5 kV line in the Pardubice model; 518 or 650 VAC inputs in the KONČAR datasheet. [2] [1] | Valve-side voltage per winding. |
| Impedance voltage (%) | Equal leakage inductance needed in both sections. [2] | Per-winding impedance. |
| No-load loss (kW) | Core loss. | Guaranteed value. |
| Load loss (kW) | Must be calculated for nonsinusoidal current. [3] | Value at converter current. |
| Insulation class | Thermal class of insulation. | Class and temperature rise. |
| Cooling method | Dry-type or liquid-immersed. | Cooling class. |
| Temperature rise (K) | Must cover the rectifier overload class, e.g. 1.5 × IN for 2 h. [1] | Rise at rated and overload duty. |
| Efficiency (%) | From losses at rated load. | Value at rated load. |
| Insulation level (kV) | Withstand levels of line and valve windings. | BIL and power frequency withstand. |
| Weight (kg) | Total and transport weight. | Weights. |
| Dimensions (L×W×H) (mm) | Footprint beside the rectifier. | Outline drawing. |
06
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
Network: [voltage; frequency; short-circuit level] Rectifier: [diode or thyristor; pulse number; DC voltage and current] Valve windings: [voltage; current; vector group; phase shift] Duty: [load class; harmonic spectrum] Construction: [dry or liquid-immersed; cooling; enclosure] Site: [altitude; ambient temperature] Standards: [IEEE C57.18.10 or IEC equivalent; tests]
Yawei's profile names ZPSC-type multi-winding phase-shifting rectifier transformers.
Company profile lists ZP(T)S, ZPSC and ZPSG-W multi-winding phase-shifting rectifier transformers and rectifier transformers alongside power and dry-type transformers.
Product scope checked 2026-10-12
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
KONČAR's 12-pulse rectifier has two three-phase inputs that require a 30° phase shift, supplied by a three-winding transformer or two double-winding transformers. [1]
The Pardubice study states the 5th, 7th, 17th and 19th primary current harmonics of the two sections are in opposition, leaving 550 Hz as the lowest on the primary. [2]
IEEE C57.18.10-2021 covers semiconductor power rectifier transformers for dedicated loads of 100 kW and above. [3]
Sources checked 2026-10-12. KONČAR publishes the datasheet of its own traction rectifier, which sets what its transformers must supply; the University of Pardubice paper studies a Czech railway 12-pulse traction rectifier; the IEEE C57.18.10 summary gives the standard's scope.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.