Replacing an HMI display that has been discontinued · panel cutout and adapter plates, communication ports that disappear, screen resolution, carrying the existing project over, and mounting-compatible third-party panels
When the operator panel on a running machine is discontinued, the new one has to fit the hole in the cabinet door, talk to the same controller over the network that is actually there, show the existing screens at a resolution they were drawn for, and run the existing project with as little rework as possible. Specify those four things from the old panel before choosing the new one.
Replacement of discontinued HMI operator panels in existing machines and cabinets: cutout and adapter plates, communication ports, display resolution, project migration and mounting-compatible third-party panels. New HMI selection, sealing and ISA-101 screen planning are covered on the Human-machine interface (HMI) page; touch technology on the HMI touchscreen page; rear-mount panels on the Rear-mount HMI panel for control cabinet doors page; washdown and hazardous-area panels on their own pages; serial display modules on the Smart display module page.
01
Rockwell Automation's migration guide 2711P-AP004F (April 2021) lists, for each PanelView Plus 6 terminal, the PanelView Plus 7 replacement, both cutouts, resolutions and the adapter plate. For the 10-inch size it names the PanelView Plus 7 Performance 10-inch terminal as "the primary replacement option for all PanelView Plus 6 1000 terminals", states that "Adapter Plates are necessary for drop-in replacement", and that "PanelView Plus 7 Performance terminals communication is only Ethernet." [1]
Rexel's Joe Amorese adds that "the products may require adapter plates as the cutout dimensions are not the same", that Rockwell "only offers adapter plates for their performance family", and that the cutout dimensions are published if the enclosure is to be modified instead. [2]
Editorial calculation from the guide's figures: the 10-inch keypad cutout narrows by 375 − 335 = 40 mm and the touch cutout by 305 − 269 = 36 mm, which is the gap the adapter plate has to close. [1]
| Old terminal | Cutout H × W | Replacement | Cutout H × W | Adapter plate | Source |
|---|---|---|---|---|---|
| PanelView Plus 6 1000 keypad, 640 × 480 | 224 × 375 mm | PanelView Plus 7 Performance 10 in., 800 × 600 | 224 × 335 mm | 2711P-RAAK10 | [1] |
| PanelView Plus 6 1000 touch | width 305 mm | PanelView Plus 7 Performance 10 in. touch | width 269 mm | 2711P-RAAT10 | [1] |
Measure the existing cutout and door thickness, and note the gasket and the IP or NEMA rating the old panel gave, before ordering a replacement or adapter plate.
02
Rexel notes that the PanelView Plus 6 "offered additional communication modules for DeviceNet, ControlNet, DH+, and DH485, and the Plus 7 only supports Ethernet/IP and Kepware server protocols or DF1 serial", leaving gateways from partners as the route for the older networks. [2] Rockwell's guide lists ControlNet, DH+ and DH-485 as add-on communication modules on PanelView Plus 6 and none on the Plus 7 terminals. [1]
Resolution changes with the panel: Rockwell's table moves the 10-inch keypad from 640 × 480 to 800 × 600, so existing screens have to be checked at the new size. [1]
A third route is a mounting-compatible panel from another maker. TR-Electronic's notion.S panels, for Siemens SIMATIC Comfort Panels TP1200 to TP2200, are described as "mechanically identical to previous Siemens models", with existing HMI projects remaining usable and engineering continuing in TIA Portal; TR-Electronic also states more than 10 years of supply. [3]
Record the old panel's model, firmware or software version, controller and network, and screen resolution; ask the supplier to state what in the project converts automatically and what needs rework.
03
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
Old panel: [make; model; catalog number; size] Cutout: [H × W; door thickness; gasket; IP/NEMA] Controller and network: [PLC; Ethernet; serial; legacy network] Screens: [resolution; software and version] Replacement: [same maker successor; adapter plate; compatible third-party] Quantity: [panels; spares]
1 company lists this product among what they make. Company figures are quoted from each company's own website; every card states where the relationship came from.
Lists industrial HMI touch screens of 4.3, 7, 10.1 and 15.6 inch for PLCs, VFDs and servo drives.
Product scope checked 2026-10-12
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
Not always; Rockwell's guide shows the PanelView Plus 7 10-inch cutout 40 mm narrower than the Plus 6 keypad and requires an adapter plate. [1]
Rexel notes the Plus 7 has no modules for DeviceNet, ControlNet, DH+ or DH485; partner gateways are the route. [2]
TR-Electronic says its notion.S panels keep existing SIMATIC Comfort Panel projects usable in TIA Portal. [3]
It can; the 10-inch PanelView Plus 6 keypad at 640 × 480 is replaced by an 800 × 600 terminal. [1]
Sources checked 2026-10-12. Rockwell Automation's PanelView Plus migration guide is read from a distributor copy; Rexel published a migration article; TR-Electronic's notion.S panels are described on a trade fair exhibitor page.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.