Process weighing · Load cell capacity and count, OIML accuracy classes, wiring, piping and calibration
A tank weighing order needs a load path and a measurement requirement. Identify empty and full loads at each support, the weigh modules and restraints, and the effects of connected pipework. Then match the cell signals, junction box and indicator to the required installed performance.
Load cells, weigh modules, junction boxes and indicators assembled into tank, hopper, vessel and process platform scales. Truck and axle scales, retail and personal scales, laboratory balances and calipers are outside this page.
01
For centred tank loads, Mettler Toledo gives C ≥ sf × (TDL + SC) / N, where C is module capacity, TDL dead load, SC scale capacity and N module count. It gives sf = 1.25 (typ.); determine the design factor for the actual installation. [1]
Editorial calculation with assumed dead load 800 kg, live capacity 2000 kg and sf = 1.25: three equally loaded supports give 1166.7 kg per module; four give 875 kg. Actual support reactions, dynamic forces and restraints require the installation design. [1]
Check the maximum reaction at each support, including agitation, pipe forces and the specified environmental loads, before selecting the module and mounting.
Provide the support drawing, dead/live loads, process forces, pipe connections, required measurement performance, environment and calibration plan.
02
OIML R 60-1:2017 classifies load cells as A, B, C or D. Table 1 gives class C 500–10000 load-cell verification intervals, B 5000–100000 and D 100–1000; C3 denotes class C with 3000 intervals. The Recommendation distinguishes a cell’s class from the measuring system in which it is used. [2]
R 60’s type-evaluation error limits use the applied load, interval v and apportioning factor pLC. A C3 cell marking alone does not establish the complete tank scale’s display division, repeatability or accuracy. Specify the cell certificate and the installed-system acceptance separately. [2]
Mettler Toledo describes junction-box summing and additional sense wires in six-wire cells, and advises against field changes to supplied cable lengths. Specify the complete signal chain and channel count. [1]
The 1996 JRC Ispra conference abstract reports tests on a 400 dm³ tank first without piping, then with piping and off-centre loading. After pipework changes, clamping optimisation and recalibration, initial repeatability with process piping attached was ±0.006% of 400 kg liquid load. This is one installation’s repeatability result. [4]
Editorial calculation: 400 kg × 0.006 / 100 = 0.024 kg, or 24 g. This does not specify accuracy, uncertainty or an acceptance limit for another weighing system. [4]
03
Flintec’s US6172309B1 describes a cantilevered shear-beam load cell with strain gauges on opposite sides of a web in a bridge circuit. The disclosed beam has a flat sensing region with gradually thickening web areas beyond it. This is a particular cell construction, not the structure of every weigh module. [3]
The patent contrasts prior designs that vary web thickness at fixed blank dimensions with its proposed approach of changing beam/web height for different ratings. It describes making the pockets and other features in one machining setup, compared with five for the prior example. These are technical disclosures, not verified manufacturing or accuracy results for a listed supplier’s cell. [3]
04
The reviewed ranges cover different supply boundaries: Zhihe and HOLI list weighing modules; other offers provide sensors, indicators or junction boxes. Define who designs and accepts the complete tank scale.
Zhihe’s module category lists tank-weighing and compression-module products. HOLI lists HH8C and HSB static modules plus an HSB dynamic module. Top Sensor lists an SD-03 shear-beam cell; Kuanyi lists shear-beam sensors including SQE, SQB and SQBL. Zhimin lists XK3190-T6 indicators, while HiWEIGH’s JB sheet describes multi-cell junction boxes.
05
The mounting carries process loads into the sensor; the electrical chain carries its signal to the indication. Specify both boundaries and include the pipework in commissioning.
| Part | Role | Fix in the order |
|---|---|---|
| Load cell / weigh module | Senses the applied load; distinguish the sensor from its mounting assembly. [2] | Capacity, classification, load direction and mating module. |
| Mounting hardware | Introduces load and provides the specified restraints. | Support reactions, movement and restraint design. |
| Cables | Carry excitation and measurement signals. [1] | Approved wiring, supplied length, routing and strain relief. |
| Junction box | Sums the specified connected cells. [1] | Channel count, signal type, matching and enclosure conditions. |
| Indicator | Converts the selected signal chain into a weight indication. | Resolution, filtering, outputs and installed acceptance. |
06
Separate per-cell ratings from the completed tank system. Record performance with the intended pipework and process configuration, rather than deriving it from a component class alone.
| Field | What it means and published values | Ask the supplier for |
|---|---|---|
| Capacity (kg) | Use per-support load and the approved design factor. | Module capacity, count and maximum reaction. |
| Accuracy / repeatability / uncertainty (g or kg) | Different system quantities; C3 is a load-cell classification. [2] | Separate definitions and acceptance limits at the intended loads. |
| Response time (ms) | The measurement chain and filtering determine settling behavior. | Update/settling conditions and process acceptance. |
| Operating temperature (°C) | The actual declared cell and electronics ranges. | Compensation range, rated conditions and special limits. |
| Output signal | Confirm analog/digital compatibility across the chain. | Cell, summing device and indicator interfaces. |
| Rated output (mV/V) | The selected analog cell’s sensitivity. | Rated value and tolerance. |
| Excitation voltage (V DC) | The selected cell and indicator combination. | Permitted voltage and loading. |
| Input resistance (Ω) | The selected bridge/excitation specification. | Value and tolerance. |
| Output resistance (Ω) | The selected signal-output specification. | Value and tolerance. |
| Insulation resistance (MΩ) | The named insulation test and conditions. | Test voltage, limit and record. |
| Safe overload (% of rated capacity) | The maker’s stated load condition. | Limit, direction and required restraint. |
| Ultimate overload (% of rated capacity) | A separate declared limit. | Definition and loading conditions. |
| Ingress protection | The selected cell, box, cable entry and indicator may differ. | Configuration-specific ratings and cleaning conditions. |
| Material | Identify sensor body, mount and wetted/exposed hardware separately. | Grades, finish and exposure suitability. |
| Piping and commissioning | The JRC case evaluated pipe effects and recalibrated after changes. [4] | Installed test plan, loads, repeatability and calibration records. |
07
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
Vessel: [drawing; supports; empty weight; full weight] Process: [static or dynamic; agitator; temperature; pressure] Accuracy: [resolution; class; legal-for-trade or not] Installation: [piping connections; support structure; wind/seismic] Electronics: [junction box; indicator; outputs; cable lengths] Calibration: [test weights; method; certificate]
Choose the weighing modules and the required sensors, indicators and summing components as an identified set. Ask who is responsible for the assembled tank scale and its installation tests.
Lists tank-weighing load cells, compression weigh modules and module kits. Confirm the support arrangement, restraints and supplied module contents.
Product scope checked 2026-10-18
Lists HH8C and HSB static weighing modules and an HSB dynamic module. Request the selected module drawing and the duty to which its rating applies.
Product scope checked 2026-10-18
Lists the SD-03 single shear-beam load cell for industrial scales. Confirm the required cell documentation and the separate vessel mounting/module scope.
Product scope checked 2026-10-18
Lists shear-beam load cells including SQE, SQB and SQBL, alongside indicator and junction-box ranges. Specify the matched components and responsibility for the complete tank scale.
Product scope checked 2026-10-18
Lists the XK3190-T6 indicator for static weighing systems with load cells. Confirm cell compatibility, outputs and the tank-system integration scope.
Product scope checked 2026-10-18
Its JB component sheet lists junction boxes for multiple load cells. Request the current model, connection scheme and enclosure specification for the selected measurement chain.
Product scope checked 2026-10-18
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
Mettler Toledo gives C ≥ sf × (dead load + scale capacity) / module count. Confirm the factor and actual support loads for the installation. [1]
C3 denotes a load cell’s class and 3000 verification intervals. The completed weighing system needs its own measurement and acceptance specification. [2]
Mettler Toledo advises against changing their supplied length in the field. Obtain the approved cable and wiring arrangement. [1]
The Flintec document discloses that particular geometry and manufacturing method; it does not establish how another supplier makes its cell. [3]
The JRC abstract reports measuring pipe influences and recalibrating after pipework/clamp changes. Its result belongs to that installation. [4]
Sources checked 2026-10-18. Mettler Toledo supplies system-design guidance. OIML R 60 concerns load cells; its portfolio contains Part 1 and other parts. Flintec discloses one shear-beam design. The JRC source is a 1996 conference abstract, not the complete paper or a supplier test report.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.