Editorial Technical Reference

Climate control system for a pressurized control room in a hazardous area (the air handling that keeps flammable gas out as well as cooling the room)

Air conditioning for a control room inside or beside a hazardous area · clean air intake, at least 25 Pa above adjacent spaces, 0.3 m/s outward through an open door, gas detection at a Zone 2 intake, loss-of-airflow and loss-of-pressure alarms, purge before re-energizing

A control room in or next to a hazardous area can hold general-purpose electrical equipment when a purging and pressurizing system keeps flammable gas out. The air handling unit that cools and ventilates the room then also does the protecting: it draws air from a clean source, holds the room above the pressure outside, and its failure has to be detected and acted on. The climate control specification therefore carries safety requirements as well as comfort and equipment cooling.

Air handling and pressurization for control rooms and other occupied rooms protected by pressurization in hazardous areas. General air handling units are covered on the Air handling unit page; fan modules on the Fan assembly for air handling units: the fan, motor and drive module page; portable units for shelters on the Environmental control unit (portable cooling and heating unit for tents, shelters and field facilities) page; pharmaceutical cleanroom air handling on the Cleanroom conditioning system (pharmaceutical HVAC air-handling unit) page; HVAC controllers on the Building automation controller (DDC controller) page.

CNFX editorial research · Sources checked October 13, 2026 · 2 sources

Compact air handling unit with its access door open showing a pleated filter, a finned coil and a belt-driven fan, with a white condensate drain pipe, orange valve and damper actuators, and insulated ducts in a plant room
Air handling unit with filter, coil, fan and actuators open for inspection

01

Clean air source, room pressure and open doors

IEC 60079-13:2017 lets the clean air supply include heating, ventilation and air conditioning equipment, and says "Any outdoor air used by heating, ventilation and air conditioning equipment shall be provided from the clean air supply." For pressurization "pb" the clean air comes from a non-hazardous area; for "pc" the intake may be in a Zone 2 area. [1]

The pressurization system "shall be capable of maintaining a pressure of at least 25 Pa in the room with respect to adjacent spaces, with 50 % of all outlets (not doors) open". Without an airlock, the outward velocity through an open door has to be at least 0.3 m/s, and pressure may drop below 25 Pa while that velocity is held. An airlock needs a continuous clean-air flow of at least five airlock volumes per hour, or gas detectors alarming at 25% of the limiting value. [1]

With the intake in a Zone 2 area, the standard requires at least one flammable gas detector with alarm in the intake and one in the room, and intake detection "arranged to shut down the intake of air containing flammable vapour or gas into the room on detection of 25 % of the limiting value". It also notes that it does not cover air quality for personnel with regard to toxicity and temperature. [1]

An EC&M article by James Stallcup and William G. Lawrence (2000), citing NFPA 496-1998, gives at least 0.1 in. of water column (25 Pa) "with all openings closed", and 60 ft/min (0.3 m/s) through open doors; the IEC figure is measured with half the outlets open, so check which standard the project follows. [2]

RequirementIEC 60079-13:2017NFPA 496-1998 as reported by EC&M
Room overpressure≥25 Pa, 50% of outlets (not doors) open≥0.1 in. w.c. (25 Pa), all openings closed
Open door without airlock≥0.3 m/s outward60 ft/min (0.3 m/s)
Airflow failure detectionAt the fan discharge, with alarmAt the fan discharge, alarm at an attended position
Before re-energizingPurge ≥10 room volumes at ≥5 air changes/h, unless verified otherwiseGas detectors, or a purge timer for at least four air changes

Name the standard the room is designed to, the hazardous zone around it and the intake location, and give the HVAC supplier the room volume, leakage paths and door arrangement.

02

Airflow loss, pressure loss and what happens to the power

Under IEC 60079-13, "Loss of air flow shall be detected at the discharge end of the fan and shall activate an alarm"; loss of pressure is sensed in the room, and the alarm may be delayed when an open door is the cause and inflow is sufficient. The pressurization system is energized independently of the room's power. [1]

For pressurization "pb", failure must cut power automatically to equipment without an acceptable EPL, or operation continues under administrative controls such as gas detectors confirming the room is below 25% of the limiting value; for "pc", power may be kept for a limited duration. [1]

EC&M's summary of NFPA 496 says a fan-running interlock is not reliable for detecting failure "because of the possibility of a broken belt or other equipment failure", and that the air system's power is taken ahead of any service disconnects feeding the control room. [2]

Ask the supplier for the airflow and differential pressure sensors, alarm and trip logic, door sensors, and the purge sequence before power is restored, and how these are tested at commissioning.

03

Pressurized control room HVAC details

Paste it into your enquiry below or into an email to a maker, then replace every bracket.

Standard: [IEC 60079-13 pb/pc; NFPA 496 type]
Area: [zone around room; intake location]
Room: [volume; doors; airlock; leakage]
Pressure: [setpoint; sensor; alarm delay]
Door flow: [velocity; door sensors]
Gas detection: [intake; room; set points]
Failure action: [trip; administrative control]
Cooling: [equipment heat; occupants; design climate]

See manufacturer records Send an enquiry through CNFX

Pressurized room HVAC sources

Manufacturer profiles associated with Climate Control System.

Sourcing Climate Control System from China?
Tell us your specification and target quantity — we will match it against manufacturer records and come back with the factories that fit.
Request manufacturers We manufacture this

Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.

Share this page

Buyer questions

What pressure must a pressurized control room hold?

IEC 60079-13:2017 requires at least 25 Pa above adjacent spaces with half the outlets (not doors) open. [1]

Can the air intake be in a hazardous area?

For pressurization pc it may be in Zone 2, with gas detectors in the intake and the room and intake shutdown at 25% of the limiting value. [1]

Is a fan-running signal enough to detect failure?

No; airflow loss is detected at the fan discharge. EC&M notes a belt can break while the motor runs. [1] [2]

How much purging before power returns?

IEC 60079-13 sets at least 10 room volumes at five air changes per hour unless a reduced volume is verified. [1]

Sources and what still needs a direct check

Sources checked 2026-10-13. IEC 60079-13:2017 is read from the public copy hosted by Public.Resource.Org; EC&M published Stallcup and Lawrence's article on NFPA 496 purging and pressurizing (2000).

  1. IEC 60079-13:2017 Explosive atmospheres — Part 13: Equipment protection by pressurized room "p" and artificially ventilated room "v" (Public.Resource.Org copy) ↗ International standard Return to text ↑
  2. J. Stallcup, W. G. Lawrence — Basics of Purging and Pressurizing Systems (EC&M, Dec. 1, 2000) ↗ Trade journal article Return to text ↑

Still to check yourself

  • Name the design standard.
  • Locate the clean air intake.
  • Set pressure and door flow.
  • Specify gas detection.
  • Define failure action.
  • Plan purge and commissioning tests.
  • Verify the legal supplier and factory.
Buyer enquiry

Request manufacturing insight for Climate Control System

Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.

Where it goes
Straight to the CNFX editorial desk, and to the manufacturer if this product is linked to a claimed profile. Nothing is broadcast to a supplier list.
Your details stay here
We do not sell or rent enquiry data, and we do not add you to a mailing list. Used only to answer this request.
No commission, no middleman
CNFX is a directory. We take no cut of any order and never negotiate on a supplier's behalf.
What to include
Share your product specifications, quantity, destination and target delivery date.

Your business information is used only to process this request.

Thank you! Your message has been sent. We'll respond within 1–3 business days.
Sorry, we couldn't send your message. Please try again, or email us at [email protected].

Need to Manufacture Climate Control System?

Compare manufacturer profiles with relevant product and process capability.

Previous Product
Cleaning-in-Place (CIP) System
Next Product
Closure Mechanism
Get QuotesChat