Editorial Technical Reference

Large-scale modular PLC with redundant CPUs (dual-rack hot standby)

Large-scale and redundant PLCs · backplane-mounted CPU, power and communication modules, dual-rack hot standby, switchover time, fieldbus I/O capacity

A large-scale modular PLC mounts its CPU, power supply and communication modules on a control backplane and reaches hundreds of I/O points through extension racks and fieldbus I/O stations. For plants that cannot stop, it can be built as two identical CPU racks linked by a synchronisation module, so the standby takes over if the primary fails. Ask three things first: what switchover time the maker states and what the HMI sees during it, how much memory and fieldbus capacity each CPU model has, and which faults trigger a switchover.

Medium- to large-scale PLCs with backplane-mounted CPU, power and communication modules, extension racks and fieldbus I/O, in single-CPU or dual-rack redundant (hot-standby) form. Choosing a CPU with local expansion modules, budgeting the 24 V supply and matching I/O to field devices for a compact or small modular controller are covered on the Programmable logic controller page; assembled control cabinets are covered on the PLC control system page. Distributed control systems, safety PLCs and HMIs are outside this page.

CNFX editorial research · Sources checked October 12, 2026 · 4 sources

Technician in a hard hat testing wiring in a control cabinet with a PLC rack of I/O modules, safety relays and rows of terminal blocks
PLC rack in a control cabinet

01

Check switchover, task scan and loop response times

HollySys describes its LK large-scale PLC as designed for medium to large-scale control systems, offered with a single CPU or a dual-rack redundant CPU design, with redundancy in CPU, power supply and network. It states less than 100 ms CPU switchover time, less than 100 μs minimum task scheduling time and less than 200 ms loop response time. [1] [2]

The two racks are tied by the LK240 redundant synchronisation module with two LC optical-fibre interfaces; HollySys lists hot-plug optical modules for 2 km (multi-mode) and 20 km (single-mode) links, and the LK922 redundant DC power module accepts 19.5 to 60 V DC. [2]

Rockwell Automation, describing its ControlLogix 5590 high-availability system, states that switchovers occur as fast as 20 ms. Its list of switchover causes covers loss of power, a major controller fault, removal, insertion or failure of any module, loss of connection between redundancy modules, and loss of an EtherNet/IP connection that leaves the module unable to see any device on the network. It also warns that FactoryTalk Linx software can lose communication with the redundant pair for up to 30 seconds during a switchover. [3]

Editorial note: a controller switchover in tens of milliseconds and an HMI or historian gap measured in seconds are different quantities; ask the supplier for both, and for how outputs behave during the transfer.

Give the supplier the process to be controlled, the I/O count by signal type, which parts must be redundant (CPU, power, network, I/O), the tolerable switchover time, the HMI and historian software, fieldbus types, and the installation environment.

02

Choose CPU capacity, I/O and programming languages

HollySys's technical data for three LK CPUs: the LK220 runs at 600 MHz with 24 MB integrated program and data memory, the LK222 at 667 MHz with 32 MB and the LK224 at 766 MHz with 64 MB. Floating-point instructions take 25, 18 and 12 ns, and bit operations 15, 10 and 7 ns. Each has 512 KB of MRAM for power-loss retention. [2]

Fieldbus capacity differs by model: up to 128 Powerlink slaves on the LK220 and 256 on the LK222 and LK224, 124 Profibus-DP slaves on each, and 16, 32 or 64 Modbus TCP master/slave connections. Each CPU has two 10/100M RJ45 ports with dual-network-port redundancy. The CPU, power and communication modules sit on 4-, 6- or 7-slot control backplanes (LK130, LK132, LK133). [2]

HollySys programs the LK in its FA-AutoThink engineering software, which it says aligns with IEC 61131-3 and supports LD, FBD, CFC, SFC and ST; tasks can be cyclic, event-triggered, state-triggered or run at full speed, and protocol configuration covers Profibus-DP, Modbus, Powerlink and EtherCAT. [2]

Editorial calculation: moving from the LK220 to the LK224 multiplies integrated memory by 64 ÷ 24 ≈ 2.7 and doubles Powerlink slave capacity (256 ÷ 128 = 2), while floating-point time falls from 25 to 12 ns, about 52% shorter. [2]

For contrast, Chitic's PCS1200 is an all-in-one compact PLC whose single CPU module accepts up to 10 extension modules, with RS232 and RS485 ports and a stated instruction time of 0.1 µs. [4] Editorial note: that is the class of controller covered on the Programmable logic controller page; the large-scale form adds backplanes, extension racks and redundancy.

03

Dual-rack redundancy in HollySys and ControlLogix controllers

The supplier linked to this page lists a large-scale PLC with dual-rack redundancy; its card links to the page reviewed. The table compares the published controllers from the sources.

Ask each supplier for the switchover time with its test conditions, which modules can be hot-swapped, and the maximum I/O per rack and per system.

Published controllerFormCPU and memoryRedundancy
HollySys LK220 / LK222 / LK224Backplane-mounted, 4–7 slot control backplanes [2]600–766 MHz; 24–64 MB [2]Dual-rack; switchover <100 ms [1]
Rockwell ControlLogix 5590 high availabilityRedundant chassis pair [3]Not reviewedSwitchover as fast as 20 ms [3]
Chitic PCS1200 (for contrast)All-in-one compact, up to 10 extension modules [4]0.1 µs per instruction [4]Not stated [4]

04

Backplane, paired CPUs and sync module that make the controller redundant

ComponentRoleFix in the order
Control backplaneHolds CPU, power and communication modules; 4, 6 or 7 slots. [2]Slot count per rack.
CPU moduleRuns the program; 600–766 MHz, 24–64 MB. [2]Model, memory, task times.
Synchronisation moduleLinks primary and standby racks over fibre. [2]Fibre type and distance.
Power moduleRedundant DC input 19.5–60 V DC on one module. [2]Input range and redundancy.
Communication modulesEthernet, Powerlink, Profibus-DP masters. [2]Protocols and counts.
Extension racks and I/O stationsReached over fieldbus; hot swap for all modules. [1] [2]I/O count, isolation, location.

05

I/O points, scan time and ports to size the redundant CPU racks

Count the digital and analog points per rack and for the whole system, and state the scan time the redundant pair must hold.

FieldWhat it means and published valuesAsk the supplier for
Processor speed (MHz)600, 667 and 766 MHz on three LK CPUs. [2]Clock and instruction times.
Memory capacity (KB)24, 32 and 64 MB integrated; 512 KB MRAM retentive. [2]Program, data and retentive memory.
Digital inputs (points)16- and 32-channel 24 V DC input modules listed. [2]Points per module and per system.
Digital outputs (points)16-channel transistor 0.5 A; 8-channel relay 2 A max. [2]Points, type and current.
Analog inputs (points)8-channel voltage or current input modules listed. [2]Points, ranges and isolation.
Operating temperature (°C)−20 to +70 °C; storage −40 to +80 °C. [1]Range for the whole system.
Power supply voltage (V DC)Redundant module 19.5–60 V DC; adapter 12–30 V DC. [2]Input range and redundancy.
Power consumption (W)Depends on module mix.Per-rack consumption.
Scan time (ms)Minimum task scheduling <100 μs; loop response <200 ms. [1]Task and loop times at your program size.
Communication interfaces (ports)2 × RJ45 per CPU; Powerlink up to 256 slaves; Profibus-DP 124. [2]Ports and slave counts.
IP ratingCabinet-mounted equipment.Rating and enclosure requirement.
Dimensions (W x H x D) (mm)Set by backplane slot count. [2]Rack dimensions.
Weight (kg)Per rack.Mass per rack.

06

Send the redundancy, I/O and network data together

Paste it into your enquiry below or into an email to a maker, then replace every bracket.

Redundancy: [CPU; power; network; I/O; tolerable switchover time]
I/O: [digital and analog counts; signal types; isolation]
CPU: [program size; task times; memory]
Networks: [Powerlink; Profibus-DP; Modbus TCP; Ethernet]
Software: [HMI; historian; batch]
Environment: [temperature; cabinet; EMC]
Documents: [IEC 61131-2 test reports; redundancy test record]

See manufacturer records Send an enquiry through CNFX

Compare large-scale PLC suppliers

This company lists a large-scale PLC with dual-rack redundancy.

HollySys
Manufacturing site to be confirmed for the order

Lists the LK large-scale PLC with single-CPU or dual-rack redundant design, alongside compact, safety and high-performance PLC lines and DCS.

Product scope checked 2026-10-12

Current product source ↗

Large-scale redundant PLC listed · profile compiled by CNFX from public sources

Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.

Share this page

Buyer questions

How fast does a redundant PLC switch to the standby CPU?

HollySys states less than 100 ms for its LK series; Rockwell states switchovers as fast as 20 ms for ControlLogix 5590 high-availability systems. [1] [3]

What causes a redundant PLC to switch over?

Rockwell lists loss of power, a major controller fault, removal, insertion or failure of any module, loss of the link between redundancy modules, and loss of an EtherNet/IP connection that leaves the module seeing no devices. [3]

How is a large-scale PLC different from a compact PLC?

A compact PLC such as Chitic's PCS1200 takes up to 10 extension modules on one CPU; a large-scale PLC such as HollySys's LK uses control backplanes, extension racks, fieldbus I/O and optional dual-rack redundancy. [4] [2]

Sources and what still needs a direct check

Sources checked 2026-10-12. HollySys publishes the product page and catalogue for its own LK PLC; Rockwell Automation publishes the user manual for its ControlLogix high-availability system; Chitic publishes data for its own compact PLC, cited for contrast.

  1. HollySys — LK Large Scale PLC ↗ Maker product page Return to text ↑
  2. HollySys — PLC Automation catalogue (2024.06): LK technical and ordering data ↗ Maker catalogue Return to text ↑
  3. Rockwell Automation — ControlLogix 5590 High Availability Systems: Controller Switchovers (1756-UM901) ↗ Maker user manual Return to text ↑
  4. Chitic — PCS1200 programmable logic controller ↗ Maker product page Return to text ↑

Still to check yourself

  • Get the stated switchover time and test conditions.
  • Ask what HMI and historian see during switchover.
  • Check memory and fieldbus capacity per CPU model.
  • Confirm hot-swap and redundant power.
  • Verify the legal supplier and factory.
Buyer enquiry

Request manufacturing insight for Programmable Logic Controller

Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.

Where it goes
Straight to the CNFX editorial desk, and to the manufacturer if this product is linked to a claimed profile. Nothing is broadcast to a supplier list.
Your details stay here
We do not sell or rent enquiry data, and we do not add you to a mailing list. Used only to answer this request.
No commission, no middleman
CNFX is a directory. We take no cut of any order and never negotiate on a supplier's behalf.
What to include
Share your product specifications, quantity, destination and target delivery date.

Your business information is used only to process this request.

Thank you! Your message has been sent. We'll respond within 1–3 business days.
Sorry, we couldn't send your message. Please try again, or email us at [email protected].

Need to Manufacture Programmable Logic Controller?

Compare manufacturer profiles with relevant product and process capability.

Previous Product
Z-axis Ram/Spindle
Last Product
Get QuotesChat