Large-scale and redundant PLCs · backplane-mounted CPU, power and communication modules, dual-rack hot standby, switchover time, fieldbus I/O capacity
A large-scale modular PLC mounts its CPU, power supply and communication modules on a control backplane and reaches hundreds of I/O points through extension racks and fieldbus I/O stations. For plants that cannot stop, it can be built as two identical CPU racks linked by a synchronisation module, so the standby takes over if the primary fails. Ask three things first: what switchover time the maker states and what the HMI sees during it, how much memory and fieldbus capacity each CPU model has, and which faults trigger a switchover.
Medium- to large-scale PLCs with backplane-mounted CPU, power and communication modules, extension racks and fieldbus I/O, in single-CPU or dual-rack redundant (hot-standby) form. Choosing a CPU with local expansion modules, budgeting the 24 V supply and matching I/O to field devices for a compact or small modular controller are covered on the Programmable logic controller page; assembled control cabinets are covered on the PLC control system page. Distributed control systems, safety PLCs and HMIs are outside this page.
01
HollySys describes its LK large-scale PLC as designed for medium to large-scale control systems, offered with a single CPU or a dual-rack redundant CPU design, with redundancy in CPU, power supply and network. It states less than 100 ms CPU switchover time, less than 100 μs minimum task scheduling time and less than 200 ms loop response time. [1] [2]
The two racks are tied by the LK240 redundant synchronisation module with two LC optical-fibre interfaces; HollySys lists hot-plug optical modules for 2 km (multi-mode) and 20 km (single-mode) links, and the LK922 redundant DC power module accepts 19.5 to 60 V DC. [2]
Rockwell Automation, describing its ControlLogix 5590 high-availability system, states that switchovers occur as fast as 20 ms. Its list of switchover causes covers loss of power, a major controller fault, removal, insertion or failure of any module, loss of connection between redundancy modules, and loss of an EtherNet/IP connection that leaves the module unable to see any device on the network. It also warns that FactoryTalk Linx software can lose communication with the redundant pair for up to 30 seconds during a switchover. [3]
Editorial note: a controller switchover in tens of milliseconds and an HMI or historian gap measured in seconds are different quantities; ask the supplier for both, and for how outputs behave during the transfer.
Give the supplier the process to be controlled, the I/O count by signal type, which parts must be redundant (CPU, power, network, I/O), the tolerable switchover time, the HMI and historian software, fieldbus types, and the installation environment.
02
HollySys's technical data for three LK CPUs: the LK220 runs at 600 MHz with 24 MB integrated program and data memory, the LK222 at 667 MHz with 32 MB and the LK224 at 766 MHz with 64 MB. Floating-point instructions take 25, 18 and 12 ns, and bit operations 15, 10 and 7 ns. Each has 512 KB of MRAM for power-loss retention. [2]
Fieldbus capacity differs by model: up to 128 Powerlink slaves on the LK220 and 256 on the LK222 and LK224, 124 Profibus-DP slaves on each, and 16, 32 or 64 Modbus TCP master/slave connections. Each CPU has two 10/100M RJ45 ports with dual-network-port redundancy. The CPU, power and communication modules sit on 4-, 6- or 7-slot control backplanes (LK130, LK132, LK133). [2]
HollySys programs the LK in its FA-AutoThink engineering software, which it says aligns with IEC 61131-3 and supports LD, FBD, CFC, SFC and ST; tasks can be cyclic, event-triggered, state-triggered or run at full speed, and protocol configuration covers Profibus-DP, Modbus, Powerlink and EtherCAT. [2]
Editorial calculation: moving from the LK220 to the LK224 multiplies integrated memory by 64 ÷ 24 ≈ 2.7 and doubles Powerlink slave capacity (256 ÷ 128 = 2), while floating-point time falls from 25 to 12 ns, about 52% shorter. [2]
For contrast, Chitic's PCS1200 is an all-in-one compact PLC whose single CPU module accepts up to 10 extension modules, with RS232 and RS485 ports and a stated instruction time of 0.1 µs. [4] Editorial note: that is the class of controller covered on the Programmable logic controller page; the large-scale form adds backplanes, extension racks and redundancy.
03
The supplier linked to this page lists a large-scale PLC with dual-rack redundancy; its card links to the page reviewed. The table compares the published controllers from the sources.
Ask each supplier for the switchover time with its test conditions, which modules can be hot-swapped, and the maximum I/O per rack and per system.
| Published controller | Form | CPU and memory | Redundancy |
|---|---|---|---|
| HollySys LK220 / LK222 / LK224 | Backplane-mounted, 4–7 slot control backplanes [2] | 600–766 MHz; 24–64 MB [2] | Dual-rack; switchover <100 ms [1] |
| Rockwell ControlLogix 5590 high availability | Redundant chassis pair [3] | Not reviewed | Switchover as fast as 20 ms [3] |
| Chitic PCS1200 (for contrast) | All-in-one compact, up to 10 extension modules [4] | 0.1 µs per instruction [4] | Not stated [4] |
04
| Component | Role | Fix in the order |
|---|---|---|
| Control backplane | Holds CPU, power and communication modules; 4, 6 or 7 slots. [2] | Slot count per rack. |
| CPU module | Runs the program; 600–766 MHz, 24–64 MB. [2] | Model, memory, task times. |
| Synchronisation module | Links primary and standby racks over fibre. [2] | Fibre type and distance. |
| Power module | Redundant DC input 19.5–60 V DC on one module. [2] | Input range and redundancy. |
| Communication modules | Ethernet, Powerlink, Profibus-DP masters. [2] | Protocols and counts. |
| Extension racks and I/O stations | Reached over fieldbus; hot swap for all modules. [1] [2] | I/O count, isolation, location. |
05
Count the digital and analog points per rack and for the whole system, and state the scan time the redundant pair must hold.
| Field | What it means and published values | Ask the supplier for |
|---|---|---|
| Processor speed (MHz) | 600, 667 and 766 MHz on three LK CPUs. [2] | Clock and instruction times. |
| Memory capacity (KB) | 24, 32 and 64 MB integrated; 512 KB MRAM retentive. [2] | Program, data and retentive memory. |
| Digital inputs (points) | 16- and 32-channel 24 V DC input modules listed. [2] | Points per module and per system. |
| Digital outputs (points) | 16-channel transistor 0.5 A; 8-channel relay 2 A max. [2] | Points, type and current. |
| Analog inputs (points) | 8-channel voltage or current input modules listed. [2] | Points, ranges and isolation. |
| Operating temperature (°C) | −20 to +70 °C; storage −40 to +80 °C. [1] | Range for the whole system. |
| Power supply voltage (V DC) | Redundant module 19.5–60 V DC; adapter 12–30 V DC. [2] | Input range and redundancy. |
| Power consumption (W) | Depends on module mix. | Per-rack consumption. |
| Scan time (ms) | Minimum task scheduling <100 μs; loop response <200 ms. [1] | Task and loop times at your program size. |
| Communication interfaces (ports) | 2 × RJ45 per CPU; Powerlink up to 256 slaves; Profibus-DP 124. [2] | Ports and slave counts. |
| IP rating | Cabinet-mounted equipment. | Rating and enclosure requirement. |
| Dimensions (W x H x D) (mm) | Set by backplane slot count. [2] | Rack dimensions. |
| Weight (kg) | Per rack. | Mass per rack. |
06
Paste it into your enquiry below or into an email to a maker, then replace every bracket.
Redundancy: [CPU; power; network; I/O; tolerable switchover time] I/O: [digital and analog counts; signal types; isolation] CPU: [program size; task times; memory] Networks: [Powerlink; Profibus-DP; Modbus TCP; Ethernet] Software: [HMI; historian; batch] Environment: [temperature; cabinet; EMC] Documents: [IEC 61131-2 test reports; redundancy test record]
This company lists a large-scale PLC with dual-rack redundancy.
Lists the LK large-scale PLC with single-CPU or dual-rack redundant design, alongside compact, safety and high-performance PLC lines and DCS.
Product scope checked 2026-10-12
Explore company information and manufacturing capabilities, then discuss the scope of your project with a relevant supplier.
HollySys states less than 100 ms for its LK series; Rockwell states switchovers as fast as 20 ms for ControlLogix 5590 high-availability systems. [1] [3]
Rockwell lists loss of power, a major controller fault, removal, insertion or failure of any module, loss of the link between redundancy modules, and loss of an EtherNet/IP connection that leaves the module seeing no devices. [3]
Sources checked 2026-10-12. HollySys publishes the product page and catalogue for its own LK PLC; Rockwell Automation publishes the user manual for its ControlLogix high-availability system; Chitic publishes data for its own compact PLC, cited for contrast.
Ask for use case, specification boundaries, supplier type, and RFQ preparation information for this product.
Compare manufacturer profiles with relevant product and process capability.